Technical data
Publication 1794-2.1 - January 2000
FLEX I/O and FLEX Integra Product Data
16 Source Input Module 1793-IV16 and -IV16S 55
16 Source Input Module 1793-IV16 and -IV16S
Wiring
Setting Input Filter Times
You can select the input filter time (FT) for channels 00 thru 11 and
channels 12 thru 15. Select the input filter time by setting the
corresponding bits in the output image table (complementary word)
for the module.
For example, to set a filter time of 4ms for an input module at address
rack 1, module group 0, set bits 05, 04, 03, 02, 01, and 00 as shown
below.
1793-IV16
0 1 2 3 4 5 6 7 8 9 10 11 14 1512 13
24 VDC SOURCE INPUT
41811
Typical Simplified Schematic for Input 0
Input
Device
+
-
24V
V
COM
A-0
Opto
Isolation
Flexbus
Interface
41501
COM
Channel Input Common Channel Input Common
0
A-0
connect to
corresponding
terminal on
row B
8
A-8
connect to
corresponding
terminal on
row B
1
A-1
9
A-9
2
A-2
10
A-10
3
A-3
11
A-11
4
A-4
12
A-12
5
A-5
13
A-13
6
A-6
14
A-14
7
A-7
15
A-15
+24V dc Power terminals V are internally connected together in the module.
24V dc
common
Common terminals COM are internally connected together in the
module.
01 2345678 9101112131415COM
COM
VVCOM COM
0 123456789101112131415
VV
COM
COM
COM
COM
1793-IV16
1793-IV16S
Where: C = common, V = +24V dc power, 0-15 = inputs
41817
41815
A
B
B
A
ATTENTION
!
Total current draw through the terminal base
unit is limited to 10A. Separate power
connections may be necessary.
41335
O:010
Write Filter Time on system startup.
FLL
Fill File
Source 36
Destination #O:010
Length 1
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
011
Write Filter Time to complement of input module.
Dec.=
44 Octal
or 36
Decimal
I:000
00
000
FT 12-15 FT 00-11