Technical data

Publication 1794-2.1 - January 2000
FLEX I/O and FLEX Integra Product Data
Fused Terminal Base Unit Cat. No. 1794-TBNF 27
Fused Terminal Base Unit Cat. No. 1794-TBNF
Wiring
ATTENTION
!
Total current draw through the terminal base unit
is limited to 10A. Separate power connections may
be necessary.
Make certain that the hook on the terminal base
you are installing is properly hooked into the
adjacent terminal base adapter. Failure to lock the
hook into the adjacent base/adapter can result in
loss of communication on the backplane.
Do not force the terminal base into the adjacent
base/adapter. Forcing the units together can bend
or break the hook and allow the units to separate
and break communication over the backplane.
On the 1794-TBNF, only even-numbered terminals
0 through 14 (row B) are fused.
1794-TBNF
40098
Shown with
fuse cover in
the “closed”
position
16 0 2 4 6 8 10 12 14 33
34 1 3 5 7 9 11 13 15 51
1794-TBNF
16
34
33
51
Even Numbered Terminals 0 thru 14
Odd Numbered Terminals 1 thru 15
16, 0, 2, 4, 6,
8, 10, 12, 14, 33
34, 1, 3, 5, 7,
9, 11, 13, 15, 51
B
C
40097
Specifications - 1794-TBNF
Number of Terminals 2 rows of 10 terminals with cover
Terminal Screw Torque 7-9 inch-pounds
Current Capacity 10A maximum
Voltage Rating 264V ac maximum
Isolation Voltage Tested at 2500V dc for 1s between user
terminals and logic side circuitry
Channel-to-channel isolation determined by
inserted module.
Fusing 8 - 5x20mm fuses (1 for each even-numbered
terminal - 0 through 14 on row B)
Shipped with 1.6A, 250V ac Slow Blow fuses
suitable for 1794-OA8 ac output module.
Refer to individual installation instructions for
fusing recommendations for other modules.
Littelfuse PN23901.6, A-B PN94171304,
SAN-O PNSD6-1.6A
General Specifications
Dimensions (with module
installed in base) HxWxD
94mm x 94mm x 69mm (3.7in x 3.7in x 2.7in)
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock Operating
Non-operating
Vibration
0 to 55
o
C (32 to 131
o
F)
-40 to 85
o
C (-40 to 185
o
F)
5 to 95% noncondensing
30g peak acceleration, 11(±1)ms pulse width
50g peak acceleration, 11(±1)ms pulse width
Tested 5g @ 10-500Hz per IEC 68-2-6
Conductors Wire Size
Category
12 gauge (4mm
2
) stranded maximum
22 gauge (0.35mm
2
) minimum
3/64 inch (1.2mm) insulation maximum
(Established by inserted module.)
1
Publication
Installation Instructions 1794-5.17
Agency Certification
1 Use this conductor category information for planning conductor routing. Refer to
publication 1770-4.1, “Industrial Automation Wiring and Grounding Guidelines for Noise
Immunity.”