Technical data

Publication 1794-2.1 - January 2000
26 Terminal Base Unit Cat. No. 1794-TBN FLEX I/O and FLEX Integra Product Data
Terminal Base Unit Cat. No. 1794-TBN
Wiring
ATTENTION
!
Total current draw through the terminal base
unit is limited to 10A. Separate power
connections may be necessary.
Make certain that the hook on the terminal base
you are installing is properly hooked into the
adjacent terminal base adapter. Failure to lock
the hook into the adjacent base/adapter can
result in loss of communication on the
backplane.
Do not force the terminal base into the adjacent
base/adapter. Forcing the units together can
bend or break the hook and allow the units to
separate and break communication over the
backplane.
16 0 2 4 6 8 10 12 14 33
34 1 3 5 7 9 11 13 15 51
1794-TBN
16
34
33
51
Even Numbered Terminals 0 thru 14
Odd Numbered Terminals 1 thru 15
16, 0, 2, 4, 6,
8, 10, 12, 14, 33
34, 1, 3, 5, 7,
9, 11, 13, 15, 51
B
C
40097
Specifications - 1794-TBN
Number of Terminals 2 rows of 10 terminals with cover
Terminal Screw Torque 7-9 inch-pounds
Current Capacity 10A maximum
Voltage Rating 264V ac maximum
Isolation Voltage Tested at 2500V dc for 1s between user terminals
and logic side circuitry
Channel-to-channel isolation determined by
inserted module.
General Specifications
Dimensions (with module
installed in base) HxWxD
94mm x 94mm x 69mm (3.7in x 3.7in x 2.7in)
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock Operating
Non-operating
Vibration
0 to 55
o
C (32 to 131
o
F)
-40 to 85
o
C (-40 to 185
o
F)
5 to 95% noncondensing
30g peak acceleration, 11(±1)ms pulse width
50g peak acceleration, 11(±1)ms pulse width
Tested 5g @ 10-500Hz per IEC 68-2-6
Conductors Wire Size
Category
12 gauge (4mm
2
) stranded maximum
22 gauge (0.35mm
2
) minimum
3/64 inch (1.2mm) insulation maximum
(Established by inserted module.)
1
Publication
Installation Instructions 1794-5.16
Agency Certification
1 Use this conductor category information for planning conductor routing. Refer to
publication 1770-4.1, “Industrial Automation Wiring and Grounding Guidelines for Noise
Immunity.”
Class I Division 2 certified
Groups A, B, C, D certified
Class I Zone 2 Group IIC certified