Technical data
Publication 1794-2.1 - January 2000
FLEX I/O and FLEX Integra Product Data
24V dc Remote I/O Adapter (up to 8 modules) Cat. No. 1794-ASB/C & /D 15
24V dc Remote I/O Adapter (up to 8 modules) Cat. No. 1794-ASB/C & /D
Wiring
The series D adapter can communicate with FLEX Integra analog
modules.
1. Connect the remote I/O cable to the removable remote I/O
connector.
2. Connect +24V dc input to the left side of the lower connector,
terminal E.
3. Connect 24V common to the left side of the upper connector,
terminal D.
4. Connections G and F are used to pass 24V dc power (G) and 24V
common (F) to the next module in the series (if required).
5. Make wiring connections as described in the installation
instructions included with the module that mounts on your
terminal base unit.
The 1794-ASB adapter module can interface a maximum of 8 I/O
modules. This adapter can be used in the mode that requires a unique
location address for each I/O module and can also be used in a mode
that allows duplicate addressing of I/O modules.
Duplicate addressing of I/O modules allows the maximum amount of
I/O in a system for a given amount of I/O image area. An input
module can have the same location address as an output module
because they complement each other. The input module uses only the
input image area corresponding to the address. The output module
uses only the output image area corresponding to the address.
ATTENTION
!
When connecting wiring, torque terminal
screws D, E, F, and G to 7-9 inch-pounds.
Description of Modes
Addressing
Type
Module Placement Rules Legal Module
Placements
Standard • 8 terminal bases per adapter
• Each terminal base
represents 1 I/O group
• Any module in any slot
Compact
16-point
addressing
• 8 terminal bases per adapter
• Each module represents 1/2
of an I/O group
• 2 modules represent 1 I/O
group
• 8 modules = 1/2 I/O rack
• A 16-point input module and a
16-point output module in an
I/O group
Compact
8-point
addressing
digital modules
• 8 terminal bases per adapter
• Each module represents 1/4
of an I/O group
• 4 modules represent 1 I/O
group
• Two 8-point input modules
and two 8-point output
modules in an I/O group
• Module type must alternate
within an I/O group: input,
output, etc.
COM
24V
1SH2
D
E
F
G
30228
Description of Modes (continued)
Compact
8-point
addressing
analog
modules
• 8 terminal bases per adapter
• Each module and adjacent
empty base represents 1/2 of
an I/O group
• Two block transfer modules
and their adjacent empty base
= 1 I/O group - An empty slot
must accompany each block
transfer module in 8-point
compact addressing
Complementary
16-point
addressing
• 8 terminal bases per adapter
• 2 modules, 1 in primary, and
1 in complement represent 1
I/O group
• Any module in any I/O position
of the primary chassis, input
modules complemented by
output modules, analog
modules complemented by
analog modules or empty base
Complementary
8-point
addressing
• 8 terminal bases per adapter
• 4 modules, 2 in the primary
and 2 in the complement,
represents 1 I/O group
• 2 inputs in a group
complemented by 2 outputs
• 2 outputs in a group
complemented by 2 inputs
• 2 block transfer modules
complemented by 2 empty
slots
• 1 block transfer module and 1
input in a group
complemented by 1 empty slot
and 1 output module
Specifications - 1794-ASB/C & /D
The 1794-ASB/C & /D adapter cannot be used with PLC-2 processors.
I/O Capacity 8 modules
Power Supply Note: In order to comply with CE Low Voltage
Directives, you must use a Safety Extra Low Voltage
(SELV) or a Protected Extra Low Voltage (PELV)
power supply to power this adapter.
Input Voltage Rating 24V dc nominal
Input Voltage Range 19.2V to 31.2V dc (includes 5% ac ripple)
Communication Rate 57.6, 115.2, 230.4k bit/s
Indicators Adapter active - green
Adapter fault - red, Local fault - red
Flexbus Output Current 640mA maximum
Isolation Voltage 500V ac between user power and flexbus
Power Consumption 450mA maximum from external 24V supply
Power Dissipation 4.6W maximum @ 31.2V dc
Thermal Dissipation 15.7 BTU/hr @ 31.2V dc
General Specifications
Dimensions HxWxD 87mm x 68mm x 69mm (3.4in x 2.7in x 2.7in)
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock Operating
Non-operating
Vibration
0 to 55
o
C (32 to 131
o
F)
-40 to 85
o
C (-40 to 185
o
F)
5 to 95% noncondensing
30g peak acceleration, 11(±1)ms pulse width
50g peak acceleration, 11(±1)ms pulse width
Tested 5g @ 10-500Hz per IEC 68-2-6
Remote I/O Cable Belden 9463 or equivalent as specified in A-B
Approved Vendor List, publication ICCG-2.2
A-B pin connector part no. 942029-03
Power Conductors
Wire Size
Category
12 gauge (4mm
2
) stranded maximum
3/64 (1.2mm) inch insulation max.
2
1
Publication
Installation Instructions
User Manual
1794-5.46
1794-6.5.9
Agency Certification
1 Use this conductor category information for planning conductor routing. Refer to
publication 1770-4.1, “Industrial Automation Wiring and Grounding Guidelines for Noise
Immunity.”
Class I Division 2 certified
Groups A, B, C, D certified
Class I Zone 2 Group IIC certified