Technical data
Publication 1794-2.1 - January 2000
12 24V dc ControlNet Adapter Cat. No. 1794-ACN15 FLEX I/O and FLEX Integra Product Data
24V dc ControlNet Adapter Cat. No. 1794-ACN15
Wiring
1. Connect the ControlNet network cable to connector, terminal
A.
2. Connect +24V dc input to the left side of the lower connector,
terminal B.
3. Connect 24V common to the left side of the upper connector,
terminal C.
4. Connections D and E are used to pass 24V dc power (E) and
24V common (D) to the next module in the series (if
required).
5. Set the network address using the 2-position thumbwheel
switch F. Valid settings range from 01 to 99. Press either the +
or - buttons to change the number.
ATTENTION
!
When connecting wiring, torque terminal screws B,
C, D, and E to 7-9 inch-pounds.
40450
CD
B
E
AF
Network
Access Port
(NAP)
Specifications - 1794-ACN15
I/O Capacity 8 modules
Connector Screw Torque 7-9 inch-pounds
Power Supply Note: In order to comply with CE Low Voltage
Directives, you must use a Safety Extra Low Voltage
(SELV) or a Protected Extra Low Voltage (PELV)
power supply to power this adapter.
Input Voltage Rating 24V dc nominal
Input Voltage Range 19.2V to 31.2V dc (includes 5% ac ripple)
Communication Rate 5M bit/s
Supports Redundant
ControlNet Cabling
No
Indicators Comm A - red/grn
I/O Status - red/grn
Programming Ports 1 RJ-45 Network Access Port (NAP) for use with
ControlNet programming cable (e.g. 1786-CP cable)
Flexbus Output Current 640mA maximum @ 5V dc
Isolation Voltage 500V ac between user power and flexbus
Power Consumption 400mA maximum from external 24V supply
Power Dissipation 4.6W maximum @ 19.2V dc
Thermal Dissipation 15.7 BTU/hr @ 19.2V dc
General Specifications
Dimensions HxWxD 87mm x 94mm x 69mm (3.4in x 3.7in x 2.7in)
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock Operating
Non-operating
Vibration
0 to 55
o
C (32 to 131
o
F)
-40 to 85
o
C (-40 to 185
o
F)
5 to 95% noncondensing
30g peak acceleration, 11(±1)ms pulse width
50g peak acceleration, 11(±1)ms pulse width
Tested 5g @ 10-500Hz per IEC 68-2-6
ControlNet Cable Belden RG-6/U Quad Shield
Power Conductors
Type
Wire Size
Category
Copper (stranded or solid)
12 gauge (4mm
2
) stranded maximum
3/64 (1.2mm) inch insulation max.
2
1
Publication
Installation Instructions 1794-5.47
Agency Certification
1 Use this conductor category information for planning conductor routing. Refer to
publication 1770-4.1, “Industrial Automation Wiring and Grounding Guidelines for Noise
Immunity.”
Class I Division 2 certified
Groups A, B, C, D certified
Class I Zone 2 Group IIC certified