Specifications
FLEX I/O Remote I/O Adapter 9
Publication
1794-5.46 – November 1998
S1 Switch Position
Rack Number
123456
PLC–3PLC–5/250PLC–51747-SN
Rack
52
ON OFF ON OFF ON OFF
Rack 53
OFF OFF ON OFF ON OFF
Rack 54
ON ON OFF OFF ON OFF
Rack 55
OFF ON OFF OFF ON OFF
Rack 56
ON OFF OFF OFF ON OFF
Rack 57
OFF OFF OFF OFF ON OFF
Rack 60
ON ON ON ON OFF OFF
Rack 61
OFF ON ON ON OFF OFF
Rack 62
ON OFF ON ON OFF OFF
Rack 63
OFF OFF ON ON OFF OFF
Rack 64
ON ON OFF ON OFF OFF
Rack 65
OFF ON OFF ON OFF OFF
Rack 66
ON OFF OFF ON OFF OFF
Rack 67
OFF OFF OFF ON OFF OFF
Rack 70
ON ON ON OFF OFF OFF
Rack 71
OFF ON ON OFF OFF OFF
Rack 72
ON OFF ON OFF OFF OFF
Rack 73
OFF OFF ON OFF OFF OFF
Rack 74
ON ON OFF OFF OFF OFF
Rack 75
OFF ON OFF OFF OFF OFF
Rack 76
ON OFF OFF OFF OFF OFF
Not Valid OFF OFF OFF OFF OFF OFF
Rack address 77 is an illegal configuration.
PLC-5/1
1 processors can scan rack 03.
PLC-5/15 and PLC-5/20 processors can scan racks 01–03.
PLC-5/25 and PLC-5/30 processors can scan racks 01–07.
PLC-5/40 and PLC-5/40L processors can scan racks 01–17.
PLC-5/60 and PLC-5/60L processors can scan racks 01–27.
PLC-5/80 processors can scan racks 01–27.
PLC-5/250 processors can scan racks 00–37.
Note 1 –
Rack switch 1–1 is used to set a mode in this adapter
. As a result. rack addresses from 40 to 76
are only available in Standard mode.