Specifications

FLEX I/O Remote I/O Adapter14
Publication
1794-5.46 – November 1998
1794-ASB
Series D Specifications
Note:
This adapter cannot be used with PLC-2 processors This adapter can
communicate with FLEX Integra analog modules.
I/O Capacity
8 modules
Power Supply
Note:
In order to comply with CE Low V
oltage
Directives, you must use a Safety Extra Low
V
oltage (SEL
V) or a Protected Extra Low
V
oltage (PELV) power supply to power this
adapter.
Input V
oltage Rating
24V dc nominal
Input Voltage Range
19.2V to 31.2V dc (includes 5% ac ripple)
Communication Rate
57.6k bps
1
15.2k bps
230.4k bps
Indicators
Adapter Active – green
Adapter fault – red
Local fault – red
Flexbus Output Current
640mA maximum
Isolation Voltage
500V ac between user power and flexbus
Power Consumption
450mA maximum from external 24V supply
Power Dissipation
4.6W maximum @ 31.2V dc
Thermal Dissipation
15.7 BTU/hr @ 31.2V dc
Environmental Conditions
Operational T
emperature
Storage T
emperature
Relative Humidity
Shock Operating
Non-operating
Vibration
0 to 55
o
C (32 to 131
o
F)
–40 to 85
o
C (–40 to 185
o
F)
5 to 95% noncondensing
30 g peak acceleration, 1
1(+
1)ms pulse width
50 g peak acceleration, 1
1(+
1)ms pulse width
T
ested 5 g @ 10–500Hz per IEC 68-2-6
Remote I/O Cable
Belden 9463 or equivalent as specified in
publication ICCG-2.2
Remote I/O Connector Plug
Part Number 942029–03
Power Conductors
Wire Size
Category
12 gauge (4mm
2
) stranded maximum
3/64 inch (1.2mm) insulation max.
2
1
Specifications continued on next page