Appendix
B
Programming the FLEX Ex I/O Modules
Using RIO
What this Chapter Contains
Read this appendix to program the 1797-IE8 and 1797-OE8
analog modules.
Enter Block Transfer
Instructions
The FLEX Ex analog I/O modules communicate with the PLC processor
through bidirectional block transfers. This is the sequential operation of
both read and write block transfer instructions.
Before you configure the module, you need to enter block transfer
instructions into your ladder logic. The following example programs
illustrate the minimum programming required for communication to take
place between the module and a PLC processor. These programs can be
modified to suit your application requirements.
A configuration block transfer write (BTW) is initiated when the analog
module is first powered up, and subsequently only when the programmer
wants to enable or disable features of the module. The configuration BTW
sets the bits which enable the programmable features of the module, such as
filters and signal ranges, etc. Block transfer reads are performed to retrieve
information from the module.
Block transfer read (BTR) programming moves status and data from the
module to the processors data table. The processor user program initiates
the request to transfer data from the module to the processor. The
transferred words contain module status, channel status and input data from
the module.
Your program should monitor status bits, block transfer read and block
transfer write activity.