User manual

Publication 1797-6.5.1 - April 1999
Calibrating Your Module 5-9
7. Record the value indicated by the channel(s) precision current meter into
the appropriate channel’s(s’) data table location.
8. Send a message to the module instructing it to Accept Value in Channel
Data Word as Min Scale Calibration on the channel(s).
9. Await an echo message from the module announcing that it has
performed Accept Value in Channel(s) Data Word(s) as Min Scale
Calibration on the channel(s).
10.Send a message to the module instructing it to perform Max Scale
Calibration (21mA) on the channel(s).
11.Await an echo message from the module announcing that it has
performed Max Scale Calibration.
12.Record the value indicated by the channel(s) precision current meter into
the appropriate channel’s(s’) data table location.
13.Send a message to the module instructing it to Accept Value in
Channel(s) Data Word(s) as Max Scale Calibration on the channel(s).
14.Await an echo message from the module announcing that it has
performed Accept Value in Channel(s) Data Word(s) as Max Scale
Calibration on the channel(s).
15.After all channels are calibrated, send a message to the module
instructing it to go to Commands Idle state.