5-4 Calibrating Your Module
For example, based on the table below, command 4 0 0 asks for zeroing the
min and max coefficients of channel 0.
$OOUHVXOWVDUHFRPSOHWHZLWKWKLV
RQHFRPPDQG
Example MODULE Calibration Commands and Data
Once the slave completes the calibration command, the module echoes back
the command and data in the MODULE response word, see the General
MODULE Response Word below. The controller is informed the calibration
sequence is complete.
6 Max Scale Calibration by
Channel
0-7 0 input = 21mA
0-7 1-15 not used
8-15 0-15 not used
36 Calibration all Channels
General Calibration all Channels 0 0 zero min scale and max scale coefficients
0 1-15 not used
Min Scale Calibration all
Channels
1 0 input = 1mA
1 1-15 not used
Max Scale Calibration all
Channels
2 0 input = 21mA
2 1-15 not used
3-15 0-15 not used
R/W Bit
1514131211109876543210
Read cmd
flag
MODULE command response MODULE response data