User manual
Publication 1797-6.5.1 - April 1999
How to Install Your FLEX Ex Analog Modules 3-7
Panel/Wall Mounting
Installation on a wall or panel consists of:
• laying out the drilling points on the wall or panel
• drilling the pilot holes for the mounting screws
• mounting the adapter mounting plate
• installing the terminal base units and securing them to the wall or panel
If you are installing your module into a terminal base unit that is already
installed, proceed to Mounting the 1797-IE8 Analog Input or 1797-OE8
Analog Output Module on the Terminal Base Unit on page 3-9.
Use the mounting kit Cat. No. 1794-NM1 for panel/wall mounting.
41547
Adapter Module
(not included)
Terminal Base Unit
(not included)
1
2
1.4
(35.5)
1 - Mounting Plate for Adapter
2 - 18 #6 self-tapping screws
(2 for the adapter, and 2
each for up to 8 modules)