User manual
Publication 1797-6.5.1 - April 1999
2-18 Understanding Configurable FLEX Ex Analog Module Features
Data Format Control
Chapter Summary
In this chapter, we told you about the FLEX Ex system and the analog I/O
modules, and how they communicate with programmable controllers. Move
to Chapter 3 to learn how to install your FLEX Ex analog module.
Data
Format
Range Resolution Full
Range
Interpretation Data Table
Value
Count per
mA
00000-20mA 0.1% of
0-20mA
0-22mA 0-22mA 0-22000 1000
00010-20mA 0.2% of
0-20mA
0-22mA 0-110% 0-11000 500
00100-20mA 0-20mA not assigned
00110-20mA 0.03% of
0-20mA
0-20mA unsigned
integer
0-65,535 3276
01004-20mA 0.1% of
4-20mA
2-22mA 2-22mA 2000-
22000
1000
01014-20mA 4-20mA not assigned
01104-20mA 4-20mA not assigned
01114-20mA 0.03% of
4-20mA
4-20mA unsigned
integer
0-65,535 4095
10000-20mA 0-20mA not assigned
10010-20mA 0-20mA not assigned
10100-20mA 0-20mA not assigned
10110-20mA 0.28% of
0-20mA
0-22mA D/A count 0-8000 363
11004-20mA not assigned
11014-20mA 0.16% of
4-20mA
3-21mA -6.25 to
+106.25%
-625 to
+10625
625
11104-20mA 0.16% of
4-20mA
2-22mA -12.5 to
+112.5%
-1250 to
+11250
625
11114-20mA 4-20mA not assigned