User manual

Publication 1797-6.5.1 - April 1999
Understanding Configurable FLEX Ex Analog Module Features 2-11
Table 2.D
1797-OE8 Data Formats
Data
Format
Format Resolution Full
Output
Range
Module Data Processing Data Table Value
(Interpretation)
Count
per mA
Analog Fault
State
0mA as
0-20mA
0.1% of
0-20mA
0-22mA 0-22000
(0-22.000mA)
1000 min=0mA
max=22mA
hold
last=hold
50%=11mA
1 % as
0-20mA
0.2% of
0-20mA
0-22mA 0-11000
(0-110.00%)
500 min=0mA
max=22mA
hold
last=hold
50%=11mA
2 0-20mA 0-22mA not assigned
3 unsigned
integer as
0-20mA
0.03% of
0-20mA
0-20mA 0-65,535
(0-22mA)
3276 min=0mA
max=20mA
hold
last=hold
50%=10mA
4mA as
4-20mA
0.1% of
4-20mA
2-22mA 2000-22000
(2.000-22.000mA)
1000 min=2mA
max=22mA
hold
last=hold
50%=12mA
5 4-20mA 4-20mA not assigned
6 4-20mA 4-20mA not assigned
7 unsigned
integer as
4-20mA
0.03% of
4-20mA
4-20mA 0-65,535
(4-20mA)
4095 min=4mA
max=20mA
hold
last=hold
50%=12mA
8 0-20mA 0-20mA not assigned
9 0-20mA 0-20mA not assigned
output =
datatable
(
1,000
)
output = 20
datatable
(
10,000
)
output = 20
datatable
(
65,535
)
output =
datatable
(
1,000
)
output = 16
datatable
(
65,535
)
+ 4