Understanding Configurable FLEX Ex Analog Module Features 2-5
5 4-20mA as
%
0.16% of
4-20mA
2-22mA -1250 - +11250
(2s complement)
(-12.50% -
+112.50%)
625 with
error
steps
6
P$ 
DV
0.17% of
4-20mA
4-22mA 0-10607
(0-106.07%)
589 with
error
steps,
under-
range not
allowed
7 4-20mA as
unsigned
integer
0.03% of
4-20mA
4-20mA 0-65,535
(4-20mA)
4095 with
error
steps
8 0-20mA not assigned all fixed
9 0-20mA not assigned all fixed
10 0-20mA not assigned all fixed
11 0-20mA as
A/D count
0.04% of
0-20mA
0-22mA 0-55000
(0-22mA)
2500 all fixed
12 4-20mA as
%
0.16% of
4-20mA
3.6-21mA -250 - +10625
(2s comp l eme nt)
(-2.50% -
+106.25%)
625 NAMUR
NE 4
all fixed
13 4-20mA
as %
0.16% of
4-20mA
3-21mA -625 - +10625
(2s comp l eme nt)
(-6.25% -
+106.25%)
625 all fixed
14 4-20mA
as %
0.16% of
4-20mA
2-22mA -1250 - +11250
(2s complement)
(-12.50% -
+112.50%)
625 all fixed
15 4-20mA not assigned all fixed
Table 2.C
1797-IE8 Data Formats
Data
Format
Format Resolution Input
Range
Module Data Processing Data Table Value
(interpretation)
Count
per mA
Error
Steps
datatable = 10,000
input-4
(
16
)
datatable = 10,000
input-4
16
IF . . . Square_Root_Threshold
input-4
16
< 10,000
Else . . . datatable = 0
datatable = 65,535
input-4
(
16
)
datatable = 55,000
input
(
22
)
datatable = 10,000
input-4
(
16
)
datatable = 10,000
input-4
(
16
)
datatable = 10,000
input-4
(
16
)