User manual
Publication 1797-6.5.1 - April 1999
1-6 About the FLEX Ex Analog Modules
Programming the Remote Fault Alarm
For the Remote Fault alarm, you must program the threshold in 0.1mA steps
at any level on the high or low end of input signal range. The Remote Fault
alarm activates if your I/O module receives input signal values of:
• 100.63% (20.1mA) to 111.88% (21.9mA) on the high end of input
signal range
RU
• -0.63% (3.9mA) to -11.88% (2.1mA) on the low end of input
signal range
Important:This alarm is only active for one band, either on the high side of
normal operation or the low side.The Remote Transmitter Error
Up/Down parameter determines which side is active.
See page 2-2 for a description of the Remote Transmitter Error
Up/Down feature.
Local Fault Alarm
The Local Fault alarm notifies you when the loop to the transmitter or field
device, if no transmitter is used, is open or shorted.
Important:Once the alarm is issued, it remains active as long as the input
signal value remains in the programmed range.
• 112.50% (22mA) or higher on the high end of input signal range - This
value indicates a short in the loop.
RU
• -12.50% (2mA) or lower on the low end of input signal range - This
value indicates an open wire condition in the loop.
The Remote Fault and Local Fault alarms are issued with the same bit
whether the cause is an under or overrange. Monitor the Overrange and
Underrange bits in your programming software to determine if the problem
is a high current or low current.
Chapter Summary
In this chapter, you learned what FLEX Ex analog I/O modules do. Move
on to Chapter 2 to learn about configurable features on your module.