Installation Instructions FLEX I/O 8 Output HART Analog Module Catalog Number 1794-OE8H, Series B Topic Page Important User Information 2 European Hazardous Location Approval 6 Environment and Enclosure 3 Prevent Electrostatic Discharge 4 North American Hazardous Location Approval 5 About the Module 7 Install the Module 7 Wire the Module 9 Ground the Module 11 Input Map 12 Configuration Map 13 Cyclic HART Input Data 16 Configuration Map (Series A Mode) 22 Extended Configuration
FLEX I/O 8 Output HART Analog Module Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://literature.rockwellautomation.com) describes some important differences between solid state equipment and hard-wired electromechanical devices.
FLEX I/O 8 Output HART Analog Module 3 Environment and Enclosure ATTENTION This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR 11.
FLEX I/O 8 Output HART Analog Module ATTENTION This product is grounded through the DIN rail to chassis ground. Use zinc plated yellow-chromate steel DIN rail to assure proper grounding. The use of other DIN rail materials (for example, aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding. Secure DIN rail to mounting surface approximately every 200 mm (7.8 in.) and use end-anchors appropriately.
FLEX I/O 8 Output HART Analog Module 5 North American Hazardous Location Approval The following information applies when operating this equipment in hazardous locations: Informations sur l’utilisation de cet équipement en environnements dangereux: Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only.
FLEX I/O 8 Output HART Analog Module European Hazardous Location Approval European Zone 2 Certification (The following applies when the product bears the Ex or EEx Marking.
FLEX I/O 8 Output HART Analog Module 7 About the Module The HART analog modules can be used with ControlNet, Ethernet and Profibus-DP (1794-APBDV1 only) adapters. When using the Series B module with a Series B profile, you must have a ControlNet adapter Revision 5.1 or higher or an Ethernet adapater Revision 4.2 or higher. For this scenario (Series A profile with a Series B Module), the data maps (input, configuration and extended configuration) are designated as Series A Mode.
FLEX I/O 8 Output HART Analog Module ATTENTION IMPORTANT Do not remove or replace a Terminal Base unit while power is applied. Interruption of the backplane can result in unintentional operation or machine motion. You must disable keying in your profile when replacing a series A module with a series B module. To install the module on a 1794 terminal base, refer to the figure and complete the following. 1.
FLEX I/O 8 Output HART Analog Module 9 Wire the Module If you connect or disconnect wiring while the field-side power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. WARNING To connect two-wire transmitter devices for 1794-TB3G and 1794-TB3GS bases, refer to the tables and figure and complete the following.
FLEX I/O 8 Output HART Analog Module 4. Connect -V to terminal 35 on the 34 to 51 row (C). 5. If continuing power to the next terminal base unit, connect a jumper from terminal 50 (+V) on this base unit to terminal 34 on the next base unit. If continuing common to the next terminal base unit, connect a jumper from terminal 51 (-V) on this base unit to terminal 35 on the next base unit.
FLEX I/O 8 Output HART Analog Module 11 Ground the Module All I/O wiring must use shielded wire. Shields must be terminated external to the module, such as bus bars and shield-terminating feed-throughs. 44862 Outputs Each output can operate an analog field device. The channels in these modules are electrically connected to each other and have a common plus-line. IMPORTANT When interconnecting several lines, you must consider the total accumulated power. 250 Ω 1794-OE8H/B +V Power Supply 21.
FLEX I/O 8 Output HART Analog Module Output Voltage/Currency Capability Voltage 20.
FLEX I/O 8 Output HART Analog Module 13 Output Map Bit Word 15 0 Res FR 14 13 12 11 1 Channel 0 Output Data 2 Channel 1 Output Data 3 Channel 2 Output Data 4 Channel 3 Output Data 5 Channel 4 Output Data 6 Channel 5 Output Data 7 Channel 6 Output Data 8 Channel 7 Output Data 10 9 8 7 Reserved 6 5 4 3 2 1 0 DD DD DD DD DD DD DD DD Ch7 Ch6 Ch5 Ch4 Ch3 Ch2 Ch1 Ch0 Where: Res = reserved Ch = channel DD = digital data FR = fault reset Configuration Map Bit Word 15 0 LFM V
FLEX I/O 8 Output HART Analog Module Configuration Map Bit Word 15 7 HART Read Back Threshold Ch7 14 13 12 11 10 9 8 8 DF DF DF DF DF DF DF DF DM Ch7 Ch6 Ch5 Ch4 Ch3 Ch2 Ch1 Ch0 Ch7 FLE AFM Ch7 Ch7 7 9 Fault Value Ch0 10 Fault Value Ch1 11 Fault Value Ch2 12 Fault Value Ch3 13 Fault Value Ch4 14 Fault Value Ch5 15 Fault Value Ch6 16 Fault Value Ch7 17 HR HR HR HR HR HR HR HR HC Ch7 Ch6 Ch5 Ch4 Ch3 Ch2 Ch1 Ch0 Ch7 Where LFM = local fault mode FE = fault enable HHE = HART handh
FLEX I/O 8 Output HART Analog Module 15 Byte Order Configuration Byte Order Byte Order Description(1) Group B Group A Bit 9 Bit 8 Bit 1 Bit 0 0 0 0 0 Little Endian Format (Default) = All data entries in true little Endian format. 1 0 1 0 Word Swap = Word swap only values requiring more then one word, for example: 32 bit float values. 0 1 0 1 Byte Swap (reserved for future implementation) = Byte swap all words in data table.
FLEX I/O 8 Output HART Analog Module Data Format - Write Words 2 and 3 Data Format Bits 15 11 7 3 14 10 6 2 Format 13 9 5 1 12 8 4 0 Signal Range User Range LO Resolution HI LO HI 20.00 0 (4 mA) 65535 (20 mA) 0.03% of 4...20 mA 22.00 0 (0 mA) 8000 (22 mA) 0.28% of 0...20 mA 7 0 1 1 1 4…20 mA as 4.00 unsigned interger 8 1 0 0 0 Not assigned 9 1 0 0 1 10 1 0 1 0 11 1 0 1 1 0...20 mA as 0.00 D/A count 12 1 1 0 0 Not assigned 13 1 1 0 1 4...20 mA as 3.00 % 21.00 -625 (-6.
FLEX I/O 8 Output HART Analog Module 17 HART Input Data Word Bit 0 Reserved 1 Reserved 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Ch7 Ch6 Ch5 Ch4 Ch3 Ch2 Ch1 Ch0 (HART Communications Status) 2 Ch0 HART Field Device Status Ch0 HART Comm Status 3 Reserved Ch0 HART Loop Status 4 Ch0 HART Primary Value (IEEE 754-1985 Single-Precision 32 bit floating point) 5 6 7 8 9 10 Ch0 HART Secondary Value (IEEE 754-1985 Single-Precision 32 bit floating point) Ch0 HART Tertiary Value (IEEE 754-198
FLEX I/O 8 Output HART Analog Module HART Input Data Word Bit 15 28 14 13 12 11 10 9 8 7 6 5 4 3 2 1 Ch2 HART Primary Value 29 30 Ch2 HART Secondary Value 31 32 Ch 2 HART Tertiary Value 33 34 Ch2 HART Fourth Value 35 36 Ch2 HART Secondary Value Units Code Ch2 HART Primary Value Units Code 37 Ch2 HART Fourth Value Ch2 HART Tertiary Value Units Code 38 Ch3 HART Field Device Status Ch3 HART Communication Status 39 Reserved Ch0 HART Loop Status 40 Ch3 HART Primary Value
FLEX I/O 8 Output HART Analog Module 19 HART Input Data Word Bit 15 58 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Ch4 HART Fourth Value 59 60 Ch4 HART Secondary Value Units Code Ch4 HART Primary Value Units Code 61 Ch4 HART Fourth Value Ch4 HART Tertiary Value Units Code 62 Ch5 HART Field Device Status Ch5 HART Communication Status 63 Reserved Ch5 HART Loop Status 64 Ch5 HART Primary Value 65 66 Ch5 Secondary Value 67 68 Ch5 Tertiary Value 69 70 Ch5 Fourth Value 71 72 Ch5 HAR
FLEX I/O 8 Output HART Analog Module HART Input Data Word Bit 15 88 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Ch7 HART Primary Value 89 90 Ch7 Secondary Value 91 92 Ch7 Tertiary Value 93 94 Ch7 Fourth Value 95 96 Ch7 HART Secondary Value Units Code Ch7 HART Primary Value Units Code 97 Ch7 HART Fourth Value Ch7 HART Tertiary Value Units Code HART Input Data Descriptions Chn: HART CMD 3 Communication Status 0: HART CMD3 Communication Disabled or No Error Chn: HART Comm Status (HAR
FLEX I/O 8 Output HART Analog Module 21 HART Input Data Descriptions Chn: HART Loop Status: Bit 0: HART enable Bit 1: Device Connected Bit 2: Response Error Bit 3: CMD 48 Update Bit 4: HART Loop Tolerance Error Bit 5: HART Update Bit 6: HART message 0: Disabled 0: Not Connected 0: No HART message failure 0: CMD 48 not updated 0: No HART Current Fault 0: HART Device information not updated 0: No new message 1: Enabled 1: Connected 1: Response ended in error 1: CMD 48 updated 1:HART Current Fault 1: HART D
FLEX I/O 8 Output HART Analog Module HART Read Back Threshold HART Read Back Decimal Bits Value 7 6 5 4 15 14 13 12 3 11 9% 9 0 1 0 0 1 10% 10 0 1 0 1 0 … … … … … … … 30% 30 1 1 1 1 0 31% 31 1 1 1 1 1 (1) 1, 2, 3, and 4 are not applicable. Values between 1 and 4 will lead the IOM to automatically use an internal value of 5%. Configuration Map (Series A Mode) Config Bit Word 15 14 13 0 LFM Res FM FM AFState AFState Ch2...3 Ch0...1 Ch2...3 Ch0...
FLEX I/O 8 Output HART Analog Module 23 The extended configuration data table is accessed (read/write) by using a MSG or CIO instruction. Refer to Field Descriptions on page 24 for more information.
FLEX I/O 8 Output HART Analog Module Secondary Master Enable (SME)/ Primary Master Inhibit (PMI) (Series A Mode) 1 (Default) Bits(1) 2 3 4 1 PMI 8, 9, 10, 11, 12, 13, 14, 15 0 0 1 SME 0, 1, 2, 3, 4, 5, 6, 7 0 1 0 1 Pulsed On Off On HART Smooth Fitler Rebuild On On Off Off HART Read Back On On Off Off Primary Master On On Off Off Secondary Master Off On Off On (1) Where: Ch 0 - bits 0 and 8; Ch 1 - bits 1 and 9; Ch 2 - bits 2 and 10; Ch 3 - bits 3 and 11; Ch 4 - bit
FLEX I/O 8 Output HART Analog Module 25 Field Descriptions Analog Fault State Determines how module reacts to faults when channel is used in Analog Normal mode. Range: 0 = go to minimum value of data range, 1 = go to maximum value of data range, 2 = hold last state, or use analog fault state value. Analog Fault State Value Specifies the fault state value of the analog output data to the module. Specific format is controlled by Module Data Format Control parameter.
FLEX I/O 8 Output HART Analog Module Field Descriptions HART Read Back When this bit is set (1), it indicates that HART communications are failing on the associated channel. Range: 0 = normal, 1 = HART communication failure. HART Communication Range: 0 = normal, 1 = HART communication is currently occurring. HART Transmitter List When this bit is set (1), it indicates that a HART field device was found during the rebuild sequence on the associated channel.
FLEX I/O 8 Output HART Analog Module 27 Cooperative Operation of the Adapter and the 1794-OE8H Output Module The ControlNet adapter, EtherNet adapter, and the FlexLogix controllers convey the Run/Program (Idle) mode and Communication Fault status directly to the 1794-OE8H module. The 1794-OE8H module monitors this information and determines its own fault state actions according to your configuration. This allows for a more simplified approach to your connections.
FLEX I/O 8 Output HART Analog Module Status Indicators I/O 1794-OE8H 8 CH HART ANALOG OUTPUT 3 O0 O1 O2 O3 O4 Input Status O5 O6 O7 PWR Power Status 44865 Interpret the Status Indicators Status Description Flashing red Channel fault Channel 0 indicator will turn red while power-up check is running Solid green Power applied to module Publication 1794-IN109D-EN-P - January 2014
FLEX I/O 8 Output HART Analog Module 29 Specifications FLEX I/O 8 Output HART Analog Module - 1794-OE8H, Series B Attribute Value Number of outputs 8 single-ended, non-isolated Module base Catalog numbers 1794-TB3G, 1794-TB3GS Resolution 13 bits Absolute accuracy 0.1% Full Scale @ 20 °C (68°F) Accuracy drift with 0.010% Full Scale for 0 °C...55 °C (32...
FLEX I/O 8 Output HART Analog Module FLEX I/O 8 Output HART Analog Module - 1794-OE8H, Series B Attribute Value Flexbus current external input(2) 5V DC 80 mA 24V DC 190 mA Power dissipation, max 6.1 W @ 31.2V DC Enclosure type rating None (open-style) Terminal base screw torque Determined by installed terminal base Wire size Determined by installed terminal base Wiring category(3) 2 - on signal ports 2 - on power ports Wire type Shielded on signal ports Thermal dissipation, max 20.
FLEX I/O 8 Output HART Analog Module 31 Environmental Attribute Value Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): -20...55 °C (-4...131 °F) Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat) IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock): –40...85 °C (–40...
Certifications Certification (when Value product is marked)(1) c-UL-us UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CE European Union 2004/108/EC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab.