5-16 Calibrate Your Module
Table 5.13 1794-OE8H Interpretation of Calibration Data Structure Content During Read Access (Pending Status)
Command Byte Item Byte Data1 Byte Data2 Byte
Status (Binary) Command Bits 0…5 (Decimal)
10 Pending 1 Calibration command number 1 is in interpretation
now
Channel-mask 0 0
2 Calibration command number 2 is in interpretation
now
3 The written min scale value of Current is in
interpretation now
Value
low-byte
Value
high-byte
4 The written min scale value of Voltage is in
interpretation now
5 The written max scale value of Current is in
interpretation now
6 The written max scale value of Voltage is in
interpretation now
7
Reserved
(1)
Reserved
(1)
Reserved
(1)
Reserved
(1)
8 All calibration values are set to default now 0 0 0
9 The specified calibration value is set to default
now
Value-identifier
10
Reserved
(2)
Reserved
(2)
Reserved
(2)
Reserved
(2)
11
Reserved
(2)
12
Reserved
(2)
13
Reserved
(2)
14 The calibration data is saved to EEPROM right now 0 0 0
15…61 The unknown command is trying to be interpreted x
2
x
2
x
2
62 The specified setup-value is written now Setup
value-identifier
Value
low-byte
Value
high-byte
63 The setup data is saved to EEPROM right now 0 0 0
(1)
Do not use. Designated for future use.
(2)
Reserved. Used during manufacture of the product. Do not use.