User manual

Publication 1794-UM063A-EN-P - March 2006
Configure the 1794-OE8H Module in RSLogix5000 Software Over the ControlNet Network F-3
Data Format Bits
3210Range Resolution Full RangeInterpretation Data Value TableCount per mA
7654
0 0 0 0 0…20 mA 0.1% of 0…20 mA 0…22 mA 0…22 mA 0…22000 1000
0 0 0 1 0…20 mA 0.2% of 0…20 mA 0…22 mA 0…110% 0…11000 500
0 0 1 0 Not Valid
0 0 1 1 0…20 mA 0.3% of 0…20 mA 0…20 mA Unsigned Integer 0…65535 3276
0 1 0 0 4…20 mA 0.1% of 4…20 mA 2…22 mA 2…22 mA 2000…22000 1000
0 1 0 1 Not Valid Not Valid Not Valid Not Valid Not Valid Not Valid
0 1 1 0 Not Valid Not Valid Not Valid Not Valid Not Valid Not Valid
0 1 1 1 4…20 mA 0.3% of 4…20 mA 4…20 mA Unsigned Integer 0…65535 4095
1 0 0 0 Not Valid
1 0 0 1 Not Valid
1 0 1 0 Not Valid
1 0 1 1 0…20 mA 0.28% of 0…20 mA 0…22 mA D/A Count 0…8000 363
1 1 0 0 Not Valid
1 1 0 1 4…20 mA 0.16% of 4…20 mA 3…21 mA -6.25…+106.25% -625…+10625 625
1 1 1 0 4…20 mA 0.16% of 4…20 mA 2…22 mA -12.5…+112.5% -1250…+11250 625
1 1 1 1 Not Valid