Configure the 1794-IE8H Module in RSLogix 5000 Software Over the ControlNet Network E-3
Data Format Bits
4321Range Resolution Full RangeInterpretation Data Value TableCount per mA
0000020 mA0.1% of 020 mA022 mA022 mA 022000 1000
0001020 mA0.2% of 020 mA022 mA0110% 0…11000 500
0010Not Valid Not Valid Not Valid Not Valid Not Valid Not Valid
0011020 mA0.3% of 020 mA020 mAUnsigned Integer 0…65535 3276
0100420 mA0.1% of 420 mA222 mA222 mA 2000…22000 1000
0101Not Valid Not Valid Not Valid Not Valid Not Valid Not Valid
0110Not Valid Not Valid Not Valid Not Valid Not Valid Not Valid
0111420 mA0.3% of 420 mA420 mAUnsigned Integer 0…65535 4095
1000Not Valid Not Valid Not Valid Not Valid Not Valid Not Valid
1001Not Valid Not Valid Not Valid Not Valid Not Valid Not Valid
1010Not Valid Not Valid Not Valid Not Valid Not Valid Not Valid
1011020 mA0.28% of 020 mA022 mAD/A Count 0…8000 363
1100Not Valid Not Valid Not Valid Not Valid Not Valid Not Valid
1101420 mA0.16% of 420 mA321 mA-6.25+106.25% -625…+10625 625
1110420 mA0.16% of 420 mA222 mA-12.5+112.5% -1250…+11250 625
1111Not Valid Not Valid Not Valid Not Valid Not Valid Not Valid