User manual
Publication 1794-UM063A-EN-P - March 2006
Configure the 1794-IE8H Module in RSLogix 5000 Software Over the ControlNet Network E-3
Data Format Bits
4321Range Resolution Full RangeInterpretation Data Value TableCount per mA
00000…20 mA0.1% of 0…20 mA0…22 mA0…22 mA 0…22000 1000
00010…20 mA0.2% of 0…20 mA0…22 mA0…110% 0…11000 500
0010Not Valid Not Valid Not Valid Not Valid Not Valid Not Valid
00110…20 mA0.3% of 0…20 mA0…20 mAUnsigned Integer 0…65535 3276
01004…20 mA0.1% of 4…20 mA2…22 mA2…22 mA 2000…22000 1000
0101Not Valid Not Valid Not Valid Not Valid Not Valid Not Valid
0110Not Valid Not Valid Not Valid Not Valid Not Valid Not Valid
01114…20 mA0.3% of 4…20 mA4…20 mAUnsigned Integer 0…65535 4095
1000Not Valid Not Valid Not Valid Not Valid Not Valid Not Valid
1001Not Valid Not Valid Not Valid Not Valid Not Valid Not Valid
1010Not Valid Not Valid Not Valid Not Valid Not Valid Not Valid
10110…20 mA0.28% of 0…20 mA0…22 mAD/A Count 0…8000 363
1100Not Valid Not Valid Not Valid Not Valid Not Valid Not Valid
11014…20 mA0.16% of 4…20 mA3…21 mA-6.25…+106.25% -625…+10625 625
11104…20 mA0.16% of 4…20 mA2…22 mA-12.5…+112.5% -1250…+11250 625
1111Not Valid Not Valid Not Valid Not Valid Not Valid Not Valid