User manual

Publication 1794-UM063A-EN-P - March 2006
C-8 Additional HART Protocol Information
11 Read unique
identifier associated
with tag
0…5 Tag (A) 0…11 As Command 0
12 Read message None 0…23 Message (32
characters)
(A)
13 Read tag descriptor,
date
None 0…5 Tag (8 characters) (A)
6…17 Descriptor (16
characters)
(A)
18…20 Date (D)
14 Read PV sensor
information
None 0…2 Sensor serial number
3 Units code for sensor
limits and minimum
span
4…7 Upper sensor limit (F)
8…11 Lower sensor limit
12…15 Minimum span
15 Read output
information
None 0 Alarm select code
1 Transfer function code
2 PV/range limits code
3…6 Upper range value
7…10 Lower range value
11…14 Damping value
(seconds)
(F)
15 Write protect code
16 Private-label
distributor code
16 Read final assembly
number
None 0…2 Final assembly
number
17 Write message 0…23 Message (32
characters)
(A) As in command
18 Write tag descriptor,
date
0…5 Tag (8 characters) (A) As in command
6…17 Descriptor (16
characters)
18…20 Date (D)
19 Write final assembly
number
0…2 Final assembly
number
As in command
(1)
Bit 2 = protocol bridge device.
(2)
Bit 0 = multisensor device, bit 1 = EEPROM control required.
(3)
Truncated after last supported variable.
Table C.5 Universal Commands
Command Data in Command Data in Reply
# Function Byte Data Type Byte Data Type