Specifications

Publication 1794-SG002D-EN-P - May 2012
88 Select FLEX Ex I/O Modules
Modules Specifications
The following section shows more detailed module specifications in comparative
groups to facilitate your selection based on your requirements.
1797-IBN16 16 Point Non-isolated NAMUR Input Module
Fault detection, fault bits in data table and status indicator LED (per
channel) blinking red (1 Hz)
Lead breakage defeat on four-channel group basis via module DIP switch
selection
Fault detection can be disabled via data table
Programmable digital input filtering 1…33 ms (OFF to ON and ON to
OFF)
All channels updated to FlexBus 500 μs
Compatible with NAMUR sensors and dry contacts
Schematic drawing of the 1797-IBN16 module
lead break defeat
Power supply
+
-
NAMUR prox
Bus
μC
FlexBus
16 Point Non-isolated NAMUR Input Module
Specification 1797-IBN16
Number of inputs 16
Input type EN 60947-5-6, NAMUR compatible
Current, on-state input, min 2.1 mA
Current, off-state input, max 1.2 mA
Hysteresis 0.2 mA
Input frequency, max 1000 Hz
Input pulse width 25μs for on or off
Load voltage, max U/V = 7.5V DC
Short circuit current 7.5 mA
Short circuit threshold current > 6 mA
Lead breakage threshold current 0.15 mA
Input delay time, OFF to ON 1 ms, 2 ms, 3 ms, 5 ms, 9 ms, 17 ms, 33 ms
(1)
Input delay time, ON to OFF 1 ms, 2 ms, 3 ms, 5 ms, 9 ms, 17 ms, 33 ms
(2)