Specifications

Publication 1794-SG002D-EN-P - May 2012
58 Select FLEX I/O Modules
FLEX I/O Counter Modules
In order to decide which FLEX I/O counter module would best suit your
application needs, you should identify the following:
What type of application the module will be used for
What field devices, signal levels, and signal type are being connected to the
counter module
Counter Module Comparison
Catalog
Number
Application Network Capability Number
of
Inputs/
Outputs
External DC Supply
Current, Nom
Power
Dissipation, Max
Thermal
Dissipation,
Max
1794-IJ2 Rational control, including:
turbine generators
motors
drives
gears
shaft
All networks
supported by FLEX I/O
2 Input
2 Output
220 mA @ 19.2V DC
180 mA @ 24V DC
140 mA @ 31.2V DC
4.5 W @ 31.2V DC 15.3 BTU/hr @
31.2V DC
1794-IJ2XT
1794-VHSC Applications including:
packaging
material handling
flow monitoring
cut-to-length
motor speed control
monitoring
ControlNet:
1794-ACN15
1794-ACNR15
EtherNet/IP:
1794-AENT
1794-AENTR
2 Input
2 Output
100 mA @ 24V DC
(1)
5W @ 31.2V DC 17.1 BTU/hr @
31.2V DC
1794-ID2 Applications including:
quality counting
positioning
speed calculations
All networks
supported by FLEX I/O
2 Input 150 mA @ 12V DC
75 mA @ 24V DC
5.0 W @ 26.4V DC 17.1 BTU/hr @
26.4V DC
1794-IP4 Applications including:
counting pulse from flow
meters
counting pulse from density
meters
quality counting
speed calculations
4 Input
(1) Does not represent power required to supply the inputs or outputs