Technical data

A-B SuperBridge Technical Reference
1
INTRODUCTION
SuperBridge (SB) is a software application that provides two-way communications between
Merrick MC²/MC³ controllers (MCs) and the Allen-Bradley (A-B) communication networks Data
Highway Plus (DH+) and Data Highway 485 (DH485). Serial communication (DF1) between
SuperBridge and a PLC is also supported. Status and variables in MCs will appear on the A-B
networks as integer and floating point files in a PLC-5 or SLC500.
SB will run on an industrially hardened personal computer compatible platform (PC), such as the
Allen-Bradley 1771-DSX2 or 1771-EIP Information Processor, under MS-DOS. Connectivity to
the DH+ network requires the addition of a DH+ communication adapter board or PC card. Up to
128 MC² controllers can be connected to one SB. On the DH+ network, SuperBridge will support
PLC-2 and PLC-5 type DH+ unsolicited messages, such as Typed Read and Write, Word Range
Read and Write, and Read-Modify-Write. In addition, MC data can be automatically exchanged
with one or more PLC-5’s and SLC5/04’s on DH+ along with supporting multiple DH485
compatible SLC500’s over the DH485 network.
This concept is far superior to the traditional method of Allen-Bradley connectivity (1771 Remote
I/O), where the MCs have to mimic an existing Allen-Bradley I/O device, and an Allen-Bradley
PLC has to be present.
PLC connectivity
The ladder programmer can access MC data in two different ways:
Copy data to PLC. SuperBridge maintains MC data in one or more PLCs. This imposes
minimal burden on the ladder programmer and PLC memory resources. Files are
continuously updated in the PLCs by the SuperBridge with MC general status, status of
digital inputs and outputs, feedrates, totals, alarms and other parameters. The ladder
programmer can access an MC² keyboard and tag specific data items for monitoring and
manipulation. The MCs are completely accessible to the PLC. This also means that the PLC
can act as an advanced version of MasterSet and as a sophisticated sub-system to weighing
controllers, all at the same time.
Unsolicited messages. The PLC requests MC data from SB. This imposes minimal burden
on the Data Highway communications bandwidth and on the PLC performance. The ladder
programmer creates message rungs to read or write data to or from SB. This method gives
the same level of control as does the copy method above, but the ladder logic programming
effort is greater. For very large systems, this method has an advantage.
It is also possible to use a combination of the two methods.
Control Room software connectivity
Most modern control room or on-line QA monitoring software packages (MMIs) such as Rockwell
Software’s RSView, WinView and WinLinx, and Intellution’s Fix Dmacs for Windows support A-B
connectivity over DH+. This support is available regardless of the presence of an Allen-Bradley
PLC system. The MMI accesses MC data just as any PLC data, normally using the “Unsolicited
messages” method described above. This makes a MC/SB installation open to almost all
modern, powerful control and QA systems. For older MMIs, SB can also impersonate a PLC-2.
MC Controllers connectivity
Up to 128 MC² or MC³ controllers can be connected to a SB, using up to four RS-485, four-wire
connections. MC² controllers must be equipped with a serial port option. A serial port can easily
be added to an existing controller. Some older software versions of the MC² controller must be