Technical data
A-B SuperBridge Technical Reference
32
MC DATA SCREEN
1 MC Data, Controller Index 2
2
3 Number of MCs configured 5 Comm Errors logged 0
4 MC in use (1 = YES, 0 = NO) 1 Fatal Comm Errors 0
5 MC WatchDog (0.1 s ticks) 200 State Machine Index 19
6 MC Revive Time (ms) 20000 MC Model/Version 30.00.HP.A
7 MC Controller Number 3 MC Current Status Running
8
9 WI Elems N12:016 Stat MCSt DI/O LRMS RDON RERR RRES XOUT
10 Pending: 0120 0003 0730 0000 0000 0000 0000 0000
11 Completed: 0120 0003 0730 0000 0000 0000 0000 0000
12 RI Elems N13:014 FTag Stg1 Stg2 Stg3 MCCT RINT EXIN
13 Pending: 002C 0090 0093 00D9 0002 00CD 0000
14 Completed: 0000 0000 0000 0000 0000 0000 0000
15 Edit Ints (hex): [ ][ ][ ][ ][ ][ ][ ]
16 WF Elems F14:016 FTag Stg1 Stg2 Stg3
17 Pending: 7.863 0.000 15.000 2.180
18 WF Elems F14:020 ProcessVal Total ReqFResult RSRV
19 Pending: 10.500 885.600 0.000 0.000
20 RF Elems F15:006 SetPoint ReqFParam Sec SetPoint
21 Pending: 6.395 7000.000 0.000
22 Edit Floats: [ ][ ][ ]
23
24 F1 F2 F3 F6 F7 F10
25 Home Screen MC Diags A-B Msgs Next MC Prev MC Exit
The MC Data Screen shows status information and current A-B file data for one MC. It is also
possible to edit the local SB content of the two control files N13 and F15. If A-B file copy is
enabled for these files, editing is meaningless, since the edited data item will be overwritten by
the next A-B file read.
Line Keyword Explanation
1 MC Controller index for data currently displayed
3 Number of
MCs
configured
Number of configured MCs.
4 In Use A 0 indicates the data for the MC is allocated, but never used. There is
normally no controller at all with this index.
5 MC
WatchDog:
The value of the local MC watchdog timer in 0.1 s. See WatchDog (page
42)
6 MC Revive
Time
How often (in ms) SB will attempt to re-establish communication with a
MC that has had a fatal (non-recoverable) communication error. See
ReviveTime (page 42)
7 MC Controller
Number
The local MC controller Number setting. See MC Communication
Parameters (page 10) and ControllerNumber (page 41)
3 Comm Errors
logged
How many recoverable (non-fatal) communication errors that have
occurred for this MC since SB was started.
4 Fatal Comm
Errors
How many fatal (non-recoverable) communication errors that have
occurred for this MC since SB was started.
5 State Machine
index
Used for telephone support. This value rapidly scans through a
seemingly random number of values.
6 MC
Model/Version
MC application program model and version. “Unknown” if the no
successful communication has taken place with the MC or if the model