Technical data
A-B SuperBridge Technical Reference
19
Fast tagged value, F14:0,8,16..(x_FTAGV)
This float contains the value of the register tagged in Fast Tag Register Number, N13:0,7,14..
(page 17). The value is updated in the fast loop.
Slow tagged values 1 - 3, F14:1-3,9-11,17-19..(x_STAG1V, x_STAG2v, x_STAG3V)
These float contains the values of the registers tagged in Slow Tag Register Number 1 - 3
N,13:1-3,8-10,15-17.. (page 17) The values are updated in the slow loop.
Process Value, F14:4,12,20..(x_PROCV)
The value in this float depends on the MC model. It is normally the feedrate. See Process Value
(page 24). The value is updated in the fast loop.
Total, F14:5,13,21..(x_TOTAL)
All MC applications support a totalizer. The current total is available in this float. The value is
updated in the fast loop.
Request Float Result F14:6,14,22..(x_FLTRES)
This float contains the value resulting from a request. See MC Control Word, N13:4,11,18.., page
17
Reserved, F14:7,15,23..
This float is reserved for future expansion.
Floating Point Control File, F15
SuperBridge will maintain another PLC type floating point file, with 3 floats per connected MC.
The purpose of this file is to make it possible for the PLC ladder or MMI programmer. The file is
read and write. The file name is F15.
The following is a specification of the three floats belonging to a certain MC.
SetPoint, F15:0,3,6..(x_SETPT)
The value in this float will be downloaded to the MC as the current setpoint, if bit 1 in the MC
Control Word, N13:4,11,18.., page 17 is set. See also Bit 8 of MC Status Word, N12:0,8,16..,
page 14
MC Request Float Parameter, F15:1,4,7..(x_FLTPAR)
The value in this float is used to hold request parameters. See MC Control Word, N13:4,11,18..,
page 17.
Secondary SetPoint, F15:2,5,8..(x_SECPT)
The value in this float will be downloaded to the MC as the current secondary setpoint, if bit 9 in
the MC Control Word, N13:4,11,18.., page 17 is set. See also Bit 10 of MC Status Word,
N12:0,8,16.., page 14 Only MC³ 24.96.EX.D or later or 30.20.EX.Beta or later supports
secondary (batch) setpoints.