Technical data
A-B SuperBridge Technical Reference
9
C:\ABIC\BIN\CFG_485
C:\ABIC\BIN\RNATSR
C:\ABIC\BIN\RNA -a8
CD SUPERB
ABDRV
There is normally no reason to alter this file if DH485 communication is to be used.
The following is an example of AUTOEXEC.BAT configured for DF1 communication.
REM AUTOEXEC.BAT
REM SuperBridge DF1 Configuration
REM 11/30/95/BPM
PATH=C:\DOS;C:\ABIC\BIN;C:\SUPERB
SET ABIC_CONFIG=C:\ABIC\BIN
C:\ABIC\BIN\DTL_DF1
C:\ABIC\BIN\CFG_DF1
C:\ABIC\BIN\RNATSR
C:\ABIC\BIN\RNA -a8
CD SUPERB
ABDRV
There is normally no reason to alter this file if DF1 communication is to be used.
This is the default CONFIG.SYS
REM CONFIG.SYS
REM SuperBridge Default 0.99
REM 01/07/97/LTM
BUFFERS=15,0
FILES=8
DEVICE=C:\DOS\INTERLNK.EXE
The INTERLNK driver load (last line) is always attempted. It will fail if no Interlink server PC is
connected to COM1 or COM2. This is for the benefit of PC card Flash EPROM disk installations.
The intersvr/interlnk utilities is the only way to transfer files to and from the SB host PC.
SB will always start at boot, showing its home screen. To be able to edit configuration files, exit
SB by pressing F10.
Assign Station Numbers
SB will act as a PLC-5 or SLC500 on Data Highway communication networks. As such, it must
be assigned an A-B style octal station number. The station number is defined in CFG_KT.INI.
Default is 71 (octal), which is for DH+ communication. The DH485 network is limited to address
37 octal. Check that there are no station number conflicts on the Data Highway network, and edit
CFG_KT.INI if needed. If more than one SB resides on the Data Highway network, at least one if
the station numbers have to be altered. See Modify PC configuration (page 5).
Verify SB startup
Connect a VGA monitor and PC keyboard to the SB host PC and reboot. Watch for error
messages as the communication drivers load and SB starts up. The load process can be made to
run step-by-step by holding down the F8 key immediately after boot. If SB starts successfully, the
SB home screen will appear.
If possible, run “WHO” or “SUPER WHO” on another device on the DH+ network. With the default
settings, SB should appear as a “TERM” device with Station Number 71, name SUPERB.