Error writing to SST ports (SST Specific)
Error Type:
Fatal
Possible Cause:
This indicates that the ports selected are not working properly, which usually results from conflicts with other devices.
Solution:
Assign a different port range and then restart the driver.
Failed to take SST Offline (SST Specific)
Error Type:
Fatal
Possible Cause:
This occurs when the driver has trouble taking the card off-line due to a bad/nonexistent device.
Solution:
1. Check for memory conflicts. If there is a conflict, try a different memory address.
2. Check for broken connections between the card and the host. Make sure that the card is installed correctly.
3. Restart the driver.
4. Restart the computer.
Invalid Station ID detected (SST Specific)
Error Type:
Fatal
Possible Cause:
This occurs when the device with the specified ID could not be located in the network.
Solution:
1. Check if the specified Device ID is correct.
2. Check for broken connections between the card and the device.
3. Check if the device is on the appropriate network.
4. Check if the device is powered on.
Protocol load error (SST Specific)
Error Type:
Fatal
Possible Cause:
This could occur for many different reasons.
1. The device may not be configured properly.
2. There might be a memory conflict.
3. There might have been a problem with the network. (temporary network hiccups)
4. The card may be corrupted.
Solution:
1. Reconfigure the device with appropriate parameters.
2. Assign different unique memory address.
3. Restart the driver.
4. Replace the card.