Specifications
62
www.kepware.com
Allen-Bradley DH+/DH-485 Device Driver Help
5. Replace the card.
Failed to locate PKTXChannel 'Channel ID' of card 'PKTX card ID'
Error Type:
Fatal
Possible Cause:
1. Card is not installed properly.
2. Card instance ID may be used by other card.
3. The parameters selected for Channel setup may be incorrect.
4. Card is corrupted.
Solution:
1. Verify all the pins are hooked into the slot comfortably.
2. Verify that the Instance ID is not used by any other PKTX card.
3. Modify the channel properties with appropriate values.
4. Replace the card.
Failed to allocate device for board '<channel>'
Error Type:
Fatal
Possible Cause:
1. The interface card is being used by another application.
2. The interface card is not functional.
3. If it is an ISA interface card, the memory address selected may be inappropriate.
Solution:
1. Uninstall any other application (such as RSLinx) that might be using the same interface card.
2. Verify that the card is functional and inserted properly in the appropriate slot.
3. Assign the correct memory address.
Error performing diagnostics test on channel <channel_name>
Error Type:
Fatal
Possible Cause:
1. Card is not installed properly
2. Card is corrupted
Solution:
1. Verify that all the pins are hooked into the slot comfortably.
2. Replace the card.
Duplicate Station (SST Specific)
Error Type:
Fatal
Possible Cause:
This indicates that there is more than one device with the same Device ID.
Solution:
Assign a different Station ID (Device ID) to one of the duplicate stations.