Specifications

61
www.kepware.com
Allen-Bradley DH+/DH-485 Device Driver Help
Failed to clear dual port memory while performing functionality test for device: 'PKTX
Card ID' Error performing diagnostic test on <Channel Name>
Error Type:
Fatal
Possible Cause:
This error may occur due to a conflict between this OPC server and any other OPC servers supporting Allen-Bradley
Data Highway drivers. For example: RSLinx.
Possible Solutions:
Make sure that all other OPC servers (e.g., RSLinx) are completely uninstalled, and then restart the PC.
M16 Diagnostic 8-bit mode failure
Error Type:
Fatal
Possible Cause:
This occurs when the jumper settings on the KTXD card are in 8 bit mode.
Solution:
Change it to 16-bit mode. Refer to KTXD user's guide for more information.
Failed to enable card for Device <Device Name>
Error Type:
Fatal
Possible Cause:
1. Network failure.
2. Memory conflict.
3. The channel properties may have been set inaccurately.
4. Corrupted card.
Solution:
1. Check for any broken links between the card and the host. Make sure that the card is inserted properly on the
appropriate slot and then restart the driver.
2. Assign a different memory base address.
3. Modify the channel properties with appropriate values.
4. Replace the card.
Failed to start Board <boardname>. Possible Resource Conflict
Error Type:
Fatal
Possible Cause:
1. Memory Conflict.
2. Temporary network problem.
3. Bad memory address selected.
4. The parameters selected for Channel setup may be incorrect.
5. Card is corrupted.
Solution:
1. Some other device may be using the same memory address. Configure device with different memory address.
2. Restart the driver.
3. Memory address selected is not within the range. Try a different memory address.
4. Modify the channel properties with appropriate values.