Allen-Bradley DH+/DH-485 Device Driver Help
Array support is not available for the specified address: '<address>'
Error Type:
Warning
Possible Cause:
A tag address that has been specified dynamically contains an array reference for an address type that doesn't support
arrays.
Solution:
Re-enter the address in the client application to remove the array reference or correct the address type.
File Corruption
Error Type:
Fatal
Possible Cause:
One or more binary files that came with your driver may have been corrupted.
Solution:
Contact Technical Support.
Interrupt not configured
Error Type:
Fatal
Possible Cause:
1. The interrupt may not be configured on the device.
2. The interrupt configured on the device may not match with the one selected in Channel setup.
Solution:
1. Enable the interrupt by setting the correct jumper/DIP switch combination.
2. Set the interrupt parameter on the chanel properties matching the one set up on the card.
Device '<device name>' is not responding
Error Type:
Warning
Possible Cause:
1. The connection between the card and the device may be broken.
2. The connection between the PC and the card may be broken.
3. The card may have been loaded with an incorrect protocol.
4. The named device may have been assigned an incorrect memory address.
5. The channel may have been set up incorrectly.
Solution:
1. Verify that the card is inserted correctly onto the right slot.
2. Verify the Device ID given to the named device matches that of the actual device.
3. Make sure the channel settings (such as baud rate, card type and etc.) match that of your card and device settings.
Unable to write to '<address>' on device '<device name>'
Error Type:
Warning