Specifications

18
www.kepware.com
Allen-Bradley DH+/DH-485 Device Driver Help
3. Under the Interface Card tab, complete the following:
Select the Board Type: Select "5136-SD-ISA" as the "Board Type" from the drop down menu next to the
"Board Type" label.
Select the Network Type: Only the DH+ network is supported for the SST cards.
Enter the Station Address: This is the unique node ID (0-77 octal for DH+ and 0-31 decimal for DH-485) of
your device. You must make sure that this ID doesn't conflict with any other node ID on the network.
Select the Baud Rate: The available baud rates are 57.6K, 115K and 230K. Select the one that matches your
device configuration.
Select the Memory Address: You must chose a unique memory address for your 5136 -SD- ISA card from the
range "A0000-FC000".
Select the I/O PORT Address: You must select the exact I/O port that you set up with the DIP switches while
installing your 5136-SD-ISA card.
Select the Interrupt: If you are using Interrupts, you must select a unique Interrupt level from the drop down
menu next to the "Interrupt" label. To check for any conflicts, check the Device Manager. If you are not using
any interrupts, select "none" from the drop down menu.