Setup guide

Chapter 3 Driver and Protocol Objects
©
Automationdirect.com 3-71 Object Reference Manual
FP error: Undefined command
The addressed module does not support this command. (for example, trying
to write to an input module) Check to see if you are sending a command
appropriate to the module.
FP error: Checksum error
This means the checksum (
CRC in this case) failed in a frame sent by
LookoutDirect. Check the LookoutDirect receive gap setting.
FP error: Input buffer overrun
The command sent to the FieldPoint module was too long. Check the
Lookout
Direct
receive gap setting.
FP error: Non-printable ASCII character received
Only characters from ASCII value 33 to 127 are permitted in FieldPoint
commands. The command is ignored.
FP error: Data field error
An insufficient or incorrect number or characters were received by the
FieldPoint module for the specified command. Check the LookoutDirect
receive gap setting.
FP error: Communications link network watchdog timed out
There has been no network traffic in the amount of time specified by your
watchdog configuration settings, and the system has reverted to its
watchdog defaults.
FP error: Specified limits invalid for the command
This includes the case where an invalid digit (hex or decimal) was received.
Check the LookoutDirect receive gap setting.
FP error: ASCII to binary conversion error
One or more ASCII characters could not be converted to binary on the
FieldPoint module. Check the LookoutDirect
receive gap setting.
FP error: Invalid device address
The command is valid, but the addressed module does not support the
command received. Check to see if you are sending a command appropriate
to the module.
FP error: Serial framing error
An improperly framed command was received by the FieldPoint module.
Check the Lookout
Direct
receive gap setting.