could be caused by an audible squelch tail occurring at the end of a radio
transmission. Try adjusting RTS delay off and CTS timeout.
No attach response within timeout period
An attempt was made to establish communications with the PLC without
any response. Check your cabling and COM port selections, power,
configuration settings, and polling addresses.
Invalid response [x]
An error in the structure of a response frame was detected. You may have
two PLCs with the same address.
Incorrect response length [x]
A response was received with an unexpected length. You may have to
increase the Receive gap Serial Port setting to ensure Lookout
Direct
is
receiving the entire message.
Incorrect response Address
A response was received with an address not matching the objects address.
You may have two master devices on the network.
SNPX ERROR—Major code: x Minor code: x
The response message contained an SNPX error code. Refer to your
GE documentation for the meaning of this particular error.