Setup guide

Chapter 3 Driver and Protocol Objects
©
Automationdirect.com 3-41 Object Reference Manual
configuration, or you can consult the Appendix B Communications
Troubleshooting Guide
in the LookoutDirect Learning Guide.
DirectLogic Protocol Status
The DirectLogic driver object monitors protocol statistics and the data can
be viewed by selecting Options >> DirectSoft Link Status. This menu
selection will only be visible in the Options menu if a DirectLogic driver
object was previously created in your lookout process. Select the correct
object from the list that appears, and then click Select. The Link Info
dialog box appears.
The Link Info dialog box is useful for troubleshooting communication
errors. Each error is time stamped and has an error name and an extended
error description. At anytime you can press the edit button to manually
change a setting on your link or to press Auto then Accept to clear the error
log. The Link Enable box allows you to turn the communications link On
and Off.
105/205/350/405 DirectLogic PLC Family Data Members
Table 3-8. 105/205/350/405 DirectLogic PLC Data Members
Data Member Type Read Write Description
Activated Logical Yes No Object-generated signal when TRUE,
this flag signifies an active5
communication connection between the
process file and the PLC.
C0 – C3777 Logical Yes Yes Control Relays – addressed in octal and
mapped to V40600 – V40777.
CT0 – CT377 Logical Yes Yes Counter status (done) bits – addressed
in octal and mapped to V41140 –
V41157
CTA0:B
CTA377:B
Numeric Yes Yes Counter current value words BCD –
addressed in octal and mapped to
V01000 – V01377