Specifications
Allen-Bradley DH+ Driver Help
A conflict has occurred on memory/ports between devices.
Solution:
1. Check for memory conflicts. If so, try different memory address.
2. Check for I/O ports conflicts. If so, try different port address.
3. The card or section of a card may be corrupted. If so, try different memory/port address.
Protocol is not reflected onto memory after being loaded on device '<device
name>'
Error Type:
Fatal
Possible Cause:
1. The device is not configured properly.
2. A memory conflict occurred.
3. A problem occurred with the network.
4. The card is corrupted.
Solution:
1. Reconfigure the device with appropriate parameters.
2. Assign a different unique memory address.
3. Restart the driver.
4. Replace the card.
SST card execution error occurred on device '<device name>'
Error Type:
Fatal
Possible Cause:
1. There may be a memory conflict.
2. There might have been a temporary problem with the network.
3. Some binary file for the driver may be corrupted.
4. The card may be corrupted.
Solution:
1. Reconfigure the device with a different memory address.
2. Restart the driver.
3. Contact Technical Support.
4. Replace the card.
Failed to allocate device for board '<channel>'
Error Type:
Fatal
Possible Cause:
1. The interface card is being used by another application.
2. The interface card is not functional.
3. If it is an ISA interface card, the memory address selected may be inappropriate.
Solution:
1. Uninstall any other application (such as RSLinx) that might be using the same interface card.
2. Verify that the card is functional and inserted properly in the appropriate slot.
3. Assign the correct memory address.