Specifications

Allen-Bradley DH+ Driver Help
Error writing to SST ports for device '<device name>'
Failed to take the SST card offline for device '<device name>'
Bad port/memory detected on SST card while loading module on device '<device name>'
Protocol is not reflected onto memory after being loaded on device '<device name>'
SST card execution error occurred on device '<device name>'
Failed to allocate device for board '<channel>'
Duplicate Station ID detected by device '<device name>'
Error Type:
Fatal
Possible Cause:
This indicates that there is more than one device with the same Device ID.
Solution:
Assign a different Station ID (Device ID) to one of the duplicate stations.
Invalid Station ID detected by device '<device name>'
Error Type:
Fatal
Possible Cause:
This occurs when the device with the specified ID could not be located in the network.
Solution:
1. Check if the specified Device ID is correct.
2. Check for broken connections between the card and the device.
3. Check if the device is on the appropriate network.
4. Check if the device is powered on.
Error writing to SST ports for device '<device name>'
Error Type:
Fatal
Possible Cause:
This indicates that the ports selected are not working properly, which usually results from conflicts with other
devices.
Solution:
Assign a different port range and then restart the driver.
Failed to take the SST card offline for device '<device name>'
Error Type:
Fatal
Possible Cause:
This occurs when the driver has trouble taking the card off-line due to a bad/nonexistent device.
Solution:
1. Check for memory conflicts. If there is a conflict, try a different memory address.
2. Check for broken connections between the card and the host. Make sure that the card is installed correctly.
3. Restart the driver.
4. Restart the computer.
Bad port/memory detected on SST card while loading module on device
'<device name>'
Error Type:
Fatal
Possible Cause: