Specifications
Allen-Bradley DH+ Driver Help
Unable to write to address '<address>' on device '<device name>'. Frame
received contains errors
Error Type:
Warning
The Error Could Be:
1. Incorrect frame size received.
2. TNS mismatch.
3. Invalid response command returned from device.
Possible Cause:
1. Misalignment of packets due to connection/disconnection between PC and device.
2. There is bad cabling connecting the devices causing noise.
Solution:
The driver will recover from this error without intervention. If this error occurs frequently, there may be an issue
with the cabling or the device itself.
Unable to write to address '<address>' on device '<device name>'.
[STS=<value>, EXT STS=<value>]
Error Type:
Warning
Possible Cause:
The address written to does not exist in the PLC.
Solution:
1. Check the status and extended status codes that are being returned by the PLC. Note that an extended status
code may not always be returned and thus the error information is contained within the status code. The codes
are displayed in hexadecimal.
2. Status code errors in the low nibble of the status code indicate errors found by the local node. Errors found by
the local node occur when the card cannot see the destination PLC on the network for some reason.
3. Status code errors in the high nibble of the status code indicate errors found by the PLC. These errors are
generated when the data location is not available in the PLC or not writeable.
Allen-Bradley Card Specific Error Messages
The following error/warning messages may be generated. Click on the link for a description of the message.
Allen-Bradley Card Specific Error Messages
Failed to locate PKTX Channel 'Channel ID' of card 'PKTX Card ID'
Failed to write to Dual Port memory for device: '<device name>'
Failed to clear dual port memory while performing functionality test
Failed to start Board <board name>. Possible Resource Conflict
M16 Diagnostic 8-bit mode failure
Failed RAM, CTC or SIO Test
Failed to enable card for device '<device name>'
Failed to perform M16 Key write for device '<device name>'
Failed to complete diagnosis while performing M16 Diagnosis for device '<device name>'
Failed to complete loading protocol file while performing M16 diagnosis for device '<device name>'
Failed to load binary resource <Resource ID> for device '<device name>'
Failed to allocate device for board '<channel>'
Error performing diagnostics test on channel '<channel name>'
Failed to locate PKTX Channel 'Channel ID' of card 'PKTX card ID'
Error Type:
Fatal
Possible Cause:
1. The card is not installed properly.
2. Card instance ID may be used by other card.
www. kepware.com