Specifications

Allen-Bradley DH+ Driver Help
Device Setup
System Restrictions
This driver does not work on 64 bit operating systems.
Supported Devices
SLC Family processors*
PLC5 series excluding the PLC5/250 series
*Address ranges have been opened up in the driver to allow for future devices. Therefore, the driver may still
support a device even if it is not listed above.
Communication Protocol
Allen-Bradley DH+/DH-485
Maximum Number of Channels and Devices
The maximum number of channels supported is 100. The maximum number of devices supported per channel is
1024.
Timeout Parameters
Connect Timeout
This parameter specifies the time that the driver will wait for a connection to be made with a device. The valid
range is 1 to 60 seconds.
Request Timeout
This parameter specifies the time that the driver will wait on a response from the device before giving up and
going on to the next request. The valid range is 100 to 300000 milliseconds.
Retry Attempts
This parameter specifies the number of times that the driver will retry a message before giving up and going on
to the next message. The valid range is 1 to 10. The default setting is 3.
See Also: SLC500 Slot Configuration
Cable Connections
SST Card Connection to the DH+ Network
www. kepware.com
32