Specifications

Allen-Bradley DH+ Driver Help
2. Select the Interface Card tab in Channel Properties.
3. Under the Interface Card tab, configure the properties.
l Board Type: Select "5136-SD-ISA" from the drop-down menu.
l Network Type: SST cards only support the DH+ network.
l Station Address: This is the device's unique Node ID: 0-77 octal for DH+ and 0-31 decimal for DH-485.
Users must make sure that this ID does not conflict with any other Node ID on the network.
l Baud Rate: The available baud rates are 57.6K, 115K and 230K. Select the rate that matches the device
configuration.
l Memory Address: Users must choose a unique memory address for the 5136 -SD- ISA card from the
range A0000-FC000.
l I/O Port Address: Users must select the exact I/O port that was selected for the DIP switches while
installing the 5136-SD-ISA card.
l Interrupt: If using interrupts, a unique interrupt level must be selected from the drop-down menu. To
check for any conflicts, check the Device Manager. If not using interrupts, select "None."