User manual
Publication 1394-5.0 — May 2000
Wiring System, Axis, and Shunt Modules, and Motors (for all systems) 3-15
Connector Locations for 5 and 10 kW System Module (Series C)
The 5 and 10 kW system module (Series C) uses connectors instead 
of IEC terminals for connecting power. You will wire the system 
using power connectors (J1, J10, and J11) that mate with plugs (P1, 
P10, and P11) conveniently located on the bottom of the system 
module. Figure 3.11 details the location of the connectors. 
Figure 3.11
Connectors for 5 and 10 kW System Module (Series C)
Note: Refer to Appendices A and B for information about three-phase 
input fusing and circuit breaker information as related to the 
power input. Refer to the section Connecting Your External 
Shunt Resistor for information about wiring the optional shunt 
resistor to the 5 and 10 kW system modules.
!
ATTENTION: To avoid personal injury and/or 
equipment damage ensure installation complies with 
specifications regarding wire types, conductor sizes, 
branch circuit protection, and disconnect devices. The 
National Electrical Code (NEC) and local codes 
outline provisions for safely installing electrical 
equipment. 
Wire: Description: Maximum wire size:
Connects to 
terminal(s):
Required 
(Y/N):
24V Logic A user-supplied 24V AC rms or 24V DC power source. Refer to 
Appendix A
 for 24V input power specifications.
3.3 mm
2
 (12 AWG)
J1-1 and
J1-2
Y
360/480V AC Input 
Power
360/480V AC, three-phase power input Refer to 
Appendix A
 for 
system specifications for rated AC input voltage, tolerance, and 
source impedance.
5.3 mm
2
 (10 AWG)
J10-1 (U)
J10-2 (V) and
J10-3 (W)
Y
Input Power Neutral Three-phase input neutral (present only on grounded power 
configurations).
5.3 mm
2
 (10 AWG)
J10-4 N
PE Ground The1394’s ground connection to the bonded system ground bar 
on the subpanel.
8.4 mm
2
 (8 AWG)
System module 
ground bar
Y
External Shunt Resistor Optional 1400W external shunt resistor used to dissipate 
excess regenerative energy from the system module.
5.3 mm
2
 (10 AWG)
J11-3 and
J11-1
N
1394 front view
System module
ground bar
1 2 3 4
1 2 3
J10
J11
1 2
J1
1394 bottom view