3-8 Wiring System, Axis, and Shunt Modules, and Motors (for all systems)
Setting the Ground Jumper in a 5 or 10 kW System Module for 
Ungrounded Power Configurations
This procedure assumes that you have bonded and mounted your 
1394x-SJT05-x or 1394x-SJT10-x system module to the subpanel and 
that there is no power applied to the system. To set the ground jumper 
for an ungrounded system:
Important: If you have grounded power distribution, you do not 
need to set the ground jumper. Go to Grounding Your 
1394 System.
1. Verify that all 24V control and 360/480V power has been 
removed from the system.
2. Open the system module door.
3.
Note: To determine the series of your module, refer to Figure P.1 
in the Preface.
For ground jumper 
settings on this 
system module:
Do this:
Series A and B
1. Locate the jumper connected to J26 and 
J27 on the circuit board behind the 
Danger label in the upper right hand 
corner of the system module (refer to 
Figure 3.4 for the jumper’s location).
2. Unplug the jumper from J26.
3. Plug the jumper in GND3.
4. Go to main step 4.
Series C
1. Unplug the ribbon cable from the input 
wiring board (refer to Figure 3.4 for 
location).
2. Remove the three control board screws.
3. Remove the control board (pull it 
straight out from system module).
4. Locate the jumper connecting J4 and J5, 
and move one end of the jumper from J5 
to J6.
5. Re-install the control board. Align the 
guide pins in the rear of the enclosure 
with holes in the control board.
6. Re-install the three control board screws 
and re-connect the ribbon cable.
7. Go to main step 4.