Configuring Your 1394 Analog Servo System 8-9
[D/A #x Value]
The unscaled value of the data that will be output 
on the D/A channel. This parameter must be the 
destination of link for any data to be output. All 
data output is treated as a signed word.
Parameter Numbers 12, 13
Parameter Group Linear List
Display Units None
Parameter Type Read/Write
Linkable Ye s
Minimum Value -32768
Maximum Value +32767
Default Value 0
[DC Link Setup]
This parameter selects the mode of operation for 
systems fault detection. Unless DC Link is 
shared, "standard" should be selected.
Parameter Numbers 50
Parameter Group Smart Sys Data
Display Units None
Parameter Type Read/Write
Change While Running No
Linkable No
Default Value 0 "standard"
Selections 0 "standard"
1 "shared w/3ph"
2 "shared - no 3ph"
[Desired BW] 
This is associated with the auto tune function and 
allows you to enter a desired velocity bandwidth 
less than or equal to the [Max Bandwidth] 
parameter as calculated by the auto tune cycle.
Parameter Numbers 252, 253, 254, 255
Parameter Group ATune Config
Display Units Hz
Parameter Type Read/Write
Change While Running Ye s
Linkable No
Minimum Value 1 Hz
Maximum Value 60 Hz
Default Value 30 Hz
[Dig Cmd Mode]
This parameter determines whether digital 
velocity commands are treated as signed 
(Bipolar) inputs, or unsigned (Unipolar). If 
unipolar operation is selected, velocity direction 
is selected by the discrete direction commands.
Parameter Numbers 22
Parameter Group Setup
Display Units None
Parameter Type Read/Write
Change While Running No
Linkable No
Default Value 0"Bipolar"
Selections 0"Bipolar"
1 "Unipolar"
[Dig Torq Ref]
This parameter is the present value of digital 
torque reference. This parameter must be the 
destination of link for any data to be output.
Parameter Numbers 212, 213, 214, 215
Parameter Group Torq Data
Display Units amps
Parameter Type Read/Write
Linkable Ye s