40 DeviceLogix for POINT I/O and ArmorPOINT I/O on DeviceNet
You can select other produced assemblies:
Produced assembly instance 4 is the first byte of produced assembly
instance 101 (Data [0]).
Produced assembly instance 111 is the first eight bytes of produced
assembly instance 101 (Data [0]…[7]).
You can select other consumed assemblies:
Consumed assembly instance 34 is the first byte of consumed assembly
instance 102 (Data [0]).
Consumed assembly instance 112 is the first eight bytes of consumed
assembly instance 102 (Data [0]…[7]).
Default Data Map - Consumed Assembly Instance 102
Message Size: 20 Bytes
Bit 76543210
Data [0] Pt 07 Pt 06 Pt 05 Pt 04 Pt 03 Pt 02 Pt 01 Pt 00
Data [1] CNB 07 CNB 06 CNB 05 CNB 04 CNB 03 CNB 02 CNB 01 CNB 00
Data [2] Reserved
Data [3]
Data [4] Consumed Network Analog Word 0
Data [5]
Data [6] Consumed Network Analog Word 1
Data [7]
Data [8] Consumed Network Analog Word 2
Data [9]
Data [10] Consumed Network Analog Word 3
Data [11]
Data [12] Consumed Network Analog Word 4
Data [13]
Data [14] Consumed Network Analog Word 5
Data [15]
Data [16] Consumed Network Analog Word 6
Data [17]
Data [18] Consumed Network Analog Word 7
Data [19]
Where: Pt = value to be applied to the output point, CNB = Consumed Network Bit