Publication 1768-UM001C-EN-P - November 2007
42 Communicate over Networks
To communicate with DH-485 devices, perform this procedure.
1. In the Controller Organizer of RSLogix 5000 programming software,
right-click your controller and select Properties.
The Controller Properties dialog appears.
2. Click the Serial Port tab.
a. From the Mode pull-down menu, choose System.
b. From the Baud Rate pull-down menu, choose 9600 or 19200 bps.
IMPORTANT
The baud rate specifies the communication rate for
the DH-485 port. All devices on the same DH-485
network must be configured for the same baud rate.