User manual

Publication 1768-UM001C-EN-P - November 2007
110 Configure PhaseManager
Minimum System
Requirements
To develop PhaseManager programs, you need:
a CompactLogix controller, firmware revision 15.0 or later.
a communication path to the controller.
RSLogix 5000 software, version 15.0 or later.
The major revision of the controller and software must match.
To enable PhaseManager support, you need the full or professional editions of
RSLogix 5000 programming software or RSLogix 5000 with PhaseManager
software (9324-RLDPMENE).
Equipment Phase
Instructions
The controller supports several equipment-phase ladder diagram (LD) and
structured text (ST) instructions.
Additional Resources
For more information about how to configure PhaseManager, refer to The
PhaseManager User Manual, publication LOGIX-UM001
.
PhaseManager Instructions
Instruction Instruction Function
PSC Signal a phase that the state routine is complete and to
proceed to the next state.
PCMD Change the state or substate of a phase.
PFL Signal a failure for a phase.
PCLF Clear the failure code of a phase.
PXRQ Initiate communication with RSBizWare Batch software.
PRNP Clear the NewInputParameters bit of a phase.
PPD Set up breakpoints within the logic of a phase.
PATT Take ownership of a phase to either:
prevent another program or RSBizWare Batch software
from commanding a phase.
make sure another program or RSBizWare Batch software
does not already own a phase.
PDET Relinquish ownership of a phase.
POVR Override a command.