User manual
Bulletin 150
Soft Starters
1-78
Visit our website: www.ab.com/catalogs
Rockwell Automation
POWER
Line Connection Delta Connection
100…240V 50/60 Hz
Control
24V AC/DC
Control
Current Rating
‡
Motor Power @
400V AC §
Current Rating
‡
Motor Power @
400V AC §
[A] [kW] [A] [kW]
Cat. No. Cat. No.
1…3 1.1 1.7…5.1 0.55…2.2
150-C3NBD 150-C3NBR
3…9 4 5.1…16 2.2…7.5
150-C9NBD 150-C9NBR
5.3…16 7.5 9.1…27.6 4…11
150-C16NBD 150-C16NBR
6.3…19 7.5 10.9…32.8 4…15
150-C19NBD 150-C19NBR
9.2…27.7 11 14.3…43 5.5…22
150-C25NBD 150-C25NBR
10…30 15 17.3…52 7.5…22
150-C30NBD 150-C30NBR
12.3…37 18.5 21…64 7.5…30
150-C37NBD 150-C37NBR
14.3…43 22 25…74 11…37
150-C43NBD 150-C43NBR
20…60 30 34.6…104 15…55
150-C60NBD 150-C60NBR
28.3…85 45 50…147 22…75
150-C85NBD 150-C85NBR
27…108 55 47…187 90
150-C108NBD 150-C108NBR
34…135 75 59…234 132
150-C135NBD 150-C135NBR
67…201 95…110 116…348 160
150-C201NBD 150-C201NBR
84…251 95…132 145…435 250
150-C251NBD 150-C251NBR
106…317 95…160 183…549 315
150-C317NBD 150-C317NBR
120…361 110…200 208…625 355
150-C361NBD 150-C361NBR
160…480 160…250 277…831 450
150-C480NBD 150-C480NBR
Motor FLA and Motor Running Current must fall within the running current range of the device to operate
properly.
‡ From series letter "B", these units can be used in the inside the delta wiring with a current range 1.73 x higher
§ Calculated using 350 % over current during starting.
1…480/831 A Range
Soft Start
Current Limit Start
Selectable Kick Start
Selectable Soft Stop
Built-In Overload Protection
Built-In SCR Bypass
For in-line or inside-the-delta configurations
Smart Motor Controllers SMC-3
Product Selection
Up to 480V AC