User manual
Bulletin 193-EC
Motor Protection
1-72
Visit our website: www.ab.com/catalogs
Rockwell Automation
POWER
CT Ratio to FLA Setting Range Correlation
Accessories
CT Ratio FLA Setting Range [A] CT Ratio FLA Setting Range [A] CT Ratio FLA Setting Range [A]
50:5 9…45 300:5 60…302 1200:5 240…1215
100:5 18…90 500:5 84…420 2500:5 450…2250
150:5 28…140 600:5 125…630 5000:5 1000…5000
200:5 42…210 800:5 172…860 — —
Add-on Accessories
Description For Use With Cat. No.
DeviceNet Configuration Terminal
Used to interface with objects on a DeviceNet
network. Includes 1 m communications cable (193-
CB1).
193-CB1 cable included.
DeviceNet
193-DNCT
1 meter communication cable, color-coded bare
leads
193-DNCT
193-CB1
1 meter communication cable, microconnector
(male) M12
193-DNCT
193-CM1
Panel Mount Adapter/Door Mount Bezel Kit for
door mounting
193-DNCT
193-DNCT-BZ1
DIN Rail/Panel Adapter
193-EC__B
193-ECPM1
193-EC_D, 193-EC_ZZ,
193-EC_ZZ
193-ECPM2
193-EC__E
193-ECPM3
AC Input Interface Module
rated 110/120V AC, 50/60 Hz
193-EC — all
592-EC — all
193-EIMD
Core Balanced Ground
Fault Sensor
Required when using either
an E1 Plus Ground Fault
Protection or Ground
Fault/Jam Module
Required for ground fault
protection with the Cat.
No. 193-EC3 overload
relay
Max. current 45 A
Hole diameter 20 mm
100-C09…100-C37
193-CBCT1
Max. current 90 A
Hole diameter 40 mm
100-C09…100-C97
193-CBCT2
Max. current 180 A
Hole diameter 63 mm
100-C09…100-C97,
100-D115…100-D180
193-CBCT3
Max. current 420 A
Hole diameter 82 mm
100-C09…100-C97,
100-D115…100-D420
193-CBCT4
Terminal Lugs
Set of two
Protection class IP2X per IEC 60529 and DIN 40
050
100-D115, 100-D140,
100-D180, 100-
D115E…D180E, 193-
EC_F, 193-EE_F
100-DTB180
100-D210...100-D420,
193-EC_G, 193-EF2C,
193-EE_G
100-DTB420
Terminal Covers
Protection class IP20 per IEC 60529 and DIN 40
050
For direct-on-line, reversing, two-speed, and wye-
delta/star-delta assemblies
100-D115…100-D180,
193-EC_F, 193-EE_F
100-DTC180
100-D210...100-D420,
193-EC_G, 193-EE_G
100-DTC420
100-D630…100-D860,
193-EC_H, 193-EE_H
100-DTC860
Phase Barriers
Set of 4
100-D630…D860, 193-
EC_H, 193-EE_H
100-DPB860
The electronic motor protection relay can be mounted separately to top-hat rail EN 50 02-35.