User manual
Bulletin 193-EC
Motor Protection
1-70
Visit our website: www.ab.com/catalogs
Rockwell Automation
POWER
DeviceNet™ communication integrated
IEC/NEMA configurations
True RMS current sensing
Single-/three-phase
LED indicators
Test/reset button
Adjustable trip class (5…30)
Motor Diagnostics
Bulletin
No.
Inputs
No.
Outputs
PM
Diagnostics
PTC
Thermistor DeviceLogix Ground Fault
193-EC1 21
—— —
193-EC2 42
Internal
(1…5 A)
193-EC3 42
External ‡
(20 mA…5 A)
193-EC5 62
—
Exter
nal ‡
(20 mA…5 A)
‡ External ground fault sensor, Cat. No. 193-CBCT_, required
Mounts to Contactor Adjustment Range [A] Cat. No.
100-C09…100-C23
0.4…2
193-EC1PB
1…5
193-EC1AB
3…15
193-EC1BB
5…25
193-EC1CB
100-C30…100-C43
1…5
193-EC1AD
3…15
193-EC1BD
5…25
193-EC1CD
9…45
193-EC1DD
100-C60…100-C97
9…45
193-EC1DE
18…90
193-EC1EE
100-D115…100-D180
28…140
193-EC1FF
42…210
193-EC1GF
100-D210…100-D420
42…210
193-EC1GG
60…302
193-EC1HG
84…420
193-EC1JG
100-D630…100-D860
125…630
193-EC1KH
172…860
193-EC1LH
Does not include terminal lugs.
Rated operating voltage IEC: 1000V AC.
Electronic Motor Protection Relays 193-EC1 – Direct Contactor Mount
E3 and E3 Plus Electronic Overload and Current Monitor Relays