User manual

Bulletin 193-T1
Motor Protection
1-65
Visit our website: www.ab.com/catalogs
Rockwell Automation
POWER
For Use With
Setting Range
[A]
‡§
Max. Back-up gL/gG fuse [A]
50 kA, 690V AC
IEC/EN 60947-4-1 Coordination
Cat. No.Type 1 Type 2
Separate mounting required
(Panel-mounted device)
35…47 160 100
193-T1DC47P
45…60 200 125
193-T1DC60P
58…75 200 125
193-T1DC75P
72…90 250 160
193-T1DC90P
Bulletin 193-T1 overload relays shall not be used with conventional DC controlled contactors. Use electronic
controlled DC versions.
To select the setting range for use in Y-Δ Starters, multiply the rated operating current of the motor by a factor of
0.58.
§ For motors with service factor of 1.15 or greater, use motor nameplate full load current. For motors with service
factor of 1.0, use 90% of the motor nameplate full load current.
Description For Use With PQ Cat. No.
DIN Rail/Panel Mounting Adapter
For separate mounting of overload relays
Snaps on to 35 mm top hat rail
193-T1AA, 193-T1AB,
193-T1AC, 193-T1BC
1
193-T1APM
Screw Adapter
For screw fixing of the 193-T1APM panel
adapter
(1 required per adapter)
193-T1APM
10
140M-C-N45
Remote Reset Solenoid
For remote reset of 193-K and 193-T1
overload relays
193-K, 193-T1 (not
for 193-T1DC_P)
1
193-T1R
External Reset Button
For enclosed, through-the-door reset
applications. Metal construction, IP66, non-
illuminated. Refer to the 800F selection
information for additional types.
All 1
800FM-R611
Reset Rod
Length 142 mm, adjustable range 141…159
mm
All 1
800F-ATR08
Reset Adapter
Expands the reset target area when using
an external reset
193-K, 193-T1 (not
for 193-T1DC_P)
1
193-RA3
Must be ordered in multiples of package quantity.
PQ = Package Quantity
[V] 24 48 110 120 125 220…240
50 Hz
D
60 Hz
D
50/60 Hz
KJ KY KF
DC
ZJ ZY ZD ZS
Coil Voltage Codes for Remote Reset Solenoid
Product Selection / Accessories
Add-On Modules
Thermal Overload Relays, continued