User manual
Bulletin 193-T1
Motor Protection
1-64
Visit our website: www.ab.com/catalogs
Rockwell Automation
POWER
Overload protection trip class 10 / 10A
Phase loss protection
Ambient temperature compensation
Auxiliary contacts (1 N.O. and 1 N.C.)
Manual/automatic reset mode selectable
Test function for auxiliary contacts
Stop button
Trip Indicator
Optional remote reset solenoid and external reset accessories
Bimetallic Overload Relays 193-T1
Product Selection
For Use With
Setting Range
[A]
‡§
Max. Back-up gL/gG fuse [A]
50 kA, 690V AC
IEC/EN 60947-4-1 Coor
dination
Cat. No.Type 1 Type 2
100-C09…100-C23
0.1…0.16 50 — 193-T1AA16
0.16…0.25 50 —
193-T1AA25
0.25…0.40 50 2
193-T1AA40
0.35…0.50 50 2
193-T1AA50
0.45…0.63 50 2
193-T1AA63
0.55…0.80 50 4
193-T1AA80
0.75…1.0 50 4
193-T1AB10
0.90…1.3 50 6
193-T1AB13
1.1…1.6 50 6
193-T1AB16
1.4…2.0 50 10
193-T1AB20
1.8…2.5 50 16
193-T1AB25
2.3…3.2 50 16
193-T1AB32
2.9…4.0 50 16
193-T1AB40
3.5…4.8 50 16
193-T1AB48
4.5…6.3 50 20
193-T1AB63
5.5…7.5 50 25
193-T1AB75
7.2…10 50 25
193-T1AC10
9.0…12.5 50 35
193-T1AC12
100-C12…100-C23 11.3…16 50 35
193-T1AC16
100-C16…100-C23
15…20 80 40
193-T1AC20
17.5…21.5 80 50
193-T1AC21
100-C23 21…25 80 50
193-T1AC25
100-C30…100-C37
15…20 80 40
193-T1BC20
17.5…21.5 80 50
193-T1BC21
21…25 80 50
193-T1BC25
24.5…30 100 63
193-T1BC30
29…36 125 63
193-T1BC36
100-C37 33…38 125 63
193-T1BC38
100-C43
17…25 100 50
193-T1CC25
24.5…36 125 80
193-T1CC36
35…47 160 100
193-T1CC47
100-C60…100-C97
35…47 160 100
193-T1DC47
45…60 200 125
193-T1DC60
100-C72…100-C97 58…75 200 125
193-T1DC75
100-C85…100-C97 72…90 250 160
193-T1DC90